2004-12-15 00:00:00BUILDING PLAN REVIEW
 PERMIT:04111429
 ADD:1900 PALM BCH LAKES BLVD
 CONT:***PLAN REVIEW***
 SHAH DROTOS & ASSOC
 TEL: (954)943-9433
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION:
  
 1) BEFOREA PERMIT CAN BE ISSUED A
 RECORDEDNOTICE OF COMMENCEMENT WILL
 BE
 REQUIRED.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE
 EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 4) FOR PLANS SUBMITTED UNDER"PERMIT
 SET"
 PLANS, SPECIFICATIONS,REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) SITE IS LOCATED IN A "FIRE
 DISTRICT",
 F102.1 NO TYPE VI CONSTRUCTION ALLOWED
 SEES701 DETAIL (2) EXTERIOR WALL OUT
 OF COMBUSTIBLES.
  
 6 ) FBC* F102.2.8PERMANENT CANOPIES/
 AWNINGS AND THEIR SUPPORTS, ON
 BUILDINGS
 LOCATED IN THE FIRE DISTRICT, SHALL BE
 OF NON-COMBUSTIBLE MATERIAL, FIRE
 RETARDANT TREATED WOOD, WOOD OF TYPE
 III
 SIZES OR OF 1-HOUR RESISTANT
 CONSTRUCTION.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 7 ) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 8) FBC* F102.2.7ARCHITECTURAL TRIM,
 ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL BE CONSTRUCTED OF APPROVED
 NON-COMBUSTIBLE MATERIALS OR FIRE
 RETARDANT TREATED WOOD.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 9) CORRECTION OF GENERAL NOTES & CODE
 COMPLIANCE, CONSTRUCTION TYPE:
 TYPE V UNSPRINKLERED NOT "B"
  
 10) DOOR # 100 PROVIDE INFORMATION ON
 THIS BEING A ACCESSIBLE DOOR AS WELL AS
 A FIRE EXIT. THIS DOOR APPEARS TO BE A
 HORIZONTAL SLIDING DOOR, IS THIS POWER
 ACTIVATED? SEE 1012.4.
  
 11) CE-3 SOUTH WALL OF BLDG IS LOCATED
 AT 15'-0" FROM PROPERTY LINE, 705.1.1.2
 OPENING PROTECTIVES, EVERY WALL WITHIN
 15'-0" OF A PROPERTY LINE SHALL BE
 EQUIPPED WITH APPROVED OPENING
 PROTECTIVES.
  
 12) A4.0 DETAILS 1& 2 TO COMPLY WITH:
 2111.1.9*PROVIDE A 1 1/2" RECESS
 FOR A WATERSTOP. FLOOR/ WALL.
  
 13) CORRECT BASES OF DESIGN UNDERS101
 A) 2001 FLORIDA BUILDING CODE
 B) WIND EXPOSURE "B" IF DESIGNED TO
 "C" HIGHER WIND PRESSURES WILL BE
 TAKEN.
  
 14) LOCAL AMENMENTS FOR ROOF SHEATHING:
 TABLE 2306.1 PALM BEACH COUNTY
 AMENDMENTS
 ROOF SHEATHING NAILING REQUIREMENTS
  
 ZONE 1 & 28D COMMON
 6" EDGES & 6" INTERMEDIATES
  
 ZONE 38DCOMMON
 4" EDGES & 6" INTERMEDIATES
  
 15) 1606.2.4 MAIN WIND FORCE RESISTING
 SYSTEM- PLANS DO NOT INDICATE A ROOF
 FRAMING PLAN AND TRUSS ANCHOR SCHEDULE
 INDICATING THE POSITIVE , NEGATIVE AND
 HORIZONTAL FORCES ACTING AGAINST THE
 TRUSSES.
  
 16) 1707.3.1 JOIST HANGERS, FRAMING
 ANCHORS & SIMILAR DEVICES SHALL BE
 TEST-
 ED IN ACCORDANCE W/ ASTM D 1761 & BE
 LABELED AND LISTED FOR THEIR LOAD
 CARRY-
 ING CAPACITY.
  
 17)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLIONS
 C) EXTERIOR GLAZED DOORS
 D) TRANSOMS
 E) STORM SHUTTERS/ IF LARGE MISSLE
  
 GLAZING IS NOT USED
 F) ROOFING ASSEMBLIES
 G) TRUSS ANCHORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18)PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE
 USED
 FOR ALL NON-IMPACT GLAZING.FBC
 1606.1.4.
  
 19)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE
 INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL
 PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 20)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN
 INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 21)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE
 LOADS
 APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 22) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY
 NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND
 TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 23) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
 24) SHEET M-2 INDICATES ROOF TOP UNITS:
 1511.7 ROOF MOUNTED MECHANICAL UNIT S
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE MECHANICAL
 EQUIPMENT, APPLIANCES AND SUP PORTS THAT
 ARE EXPOSED TO WIND SHALL BE DESIGNED
 AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 25)1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 26)1503.4.2 OVERFLOW DRAINS SHALL BE THE
 SAME SIZE AS ROOF DRAINS, INSTALLED WITH
 THE INLET FLOW LINE LOCATED 2" ABOVE THE
 LOWEST POINT OF THE ROOF LINE. OVERFLOW
 SCUPPERS SHALL BE A MINIMUM OF 4"IN
 HEIGTH AND SHALL BE PLACED IN WALLS OR
 PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF
 SURFACE.
  
 27)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 THE EXISTING BUILDING WILL BE
 DEMOLISHED, REQUIRE A CERTIFICATE OF
 COMPLETION FOR THE DEMOLITION WORK. IN
 DOING THIS YOU SHALL RECEIVE A CREDIT AT
 TIME OF IMPACT FEE ASSESSMENT.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026