| 2005-04-11 00:00:00 | |
| | |
| | ************ UNSAT **************** |
| | |
| | |
| | *** PLEASE SEE NOTES BELOW.*** |
| | |
| | 1)NOTE: PLEASE SEE REVIEW DATED 12/15/04 |
| | PLEASE SEE THE BELOW COMMENTS FOR GEN |
| | AND ASSCOIATED EQUIPMENT. |
| | |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT ALLMANUFACTURE |
| | SPEC SHEETS SHOWING ALL INFORMATION FOR |
| | NEW PROPOSED GENERATOR, ATS. PLEASE |
| | PROVIDE PRIME MOVER INFORMATION. |
| | PLEASE ALSO PLANS WILL NOW BE CHECKED |
| | FOR ZONING REVIEW AS THIS WAS PREVIOUSLY |
| | A COMMENT FROM ZOING FOR LOCATION OF |
| | GENERATOR. |
| | |
| | |
| | 2)NOTE: PLEASE SEE MAIN FOR GENERATOR IS |
| | SHOWN IN TENANT SPACE AND NOT GROUPED OR |
| | IN CLOSE PROXIMITY OF MAIN ELECTRICAL |
| | ROOM OR OTHER MAINS. PLEASE SEE MAIN FOR |
| | GENERATOR "WILL BE " REQUIRED IN CLOSE |
| | PROXIMITY OF EXISTING MAINS 1OF 2 AND |
| | 2OF 2. |
| | THIS WAS PREVIOUSLY NOTED AND NOT |
| | ACCEPPTABLE BY THIS OFFICE OR FIRE |
| | MARSHAL'S OFFICE. |
| | PLEASE PROVIDE MORE INFORMATION ON |
| | THIS. |
| | 230.72,230.76,230.79.ETC. |
| | |
| | 3)NOTE: PLEASE SEE 700.7D, 230.95,240.13 |
| | FOR GROUND FAULT REQUIREMNETS AND |
| | SIGNALS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |