| 2005-01-04 00:00:00 | DENIED: |
| | 1.PLAN SHEET C-1 INDICATES OCCUPANCY |
| | AS 410 PEOPLE WHEREAS THE O.A. |
| | CALCULATIONS PROVIDED (M0.1) IS ONLY |
| | DESIGNED FOR 292 PEOPLE. |
| | |
| | 2.PLAN SHEET SP-1 BUILDING DATA |
| | SPECIFICATIONS, CLASSIFICATION AS |
| | FACTORY-INDUSTRIAL; PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION: |
| | 1) WHAT WILL BE MANUFACTURED |
| | 2) INDICATE ANY HAZARDOUS CHEMICALS |
| | THAT |
| | MAY BE PRESENT OR STORED. |
| | |
| | 3.THE FOLLOWING ROOMS ARE INDICATED |
| | AS |
| | HAVING A FIRE RESISTANCE RATING: 144, |
| | 147, 147A, 148, 149, 151, 152, 154E, |
| | 162, 163, 165B, 167, 168, 169, 172, |
| | 195A.PLAN SHEET M2.1 DOES NOT |
| | INDICATE |
| | FIRE DAMPERS ON ANY PENETRATIONS.PER |
| | 2001 FBC(M)607.6, PLANS SHALL PROVIDE |
| | SPECIFIC LOCATIONS FOR EACH FIRE DAMPER |
| | & ACCESS DOOR. |
| | |
| | 4.PLAN SHEET M7.2 THE HVAC SUPPORT |
| | DETAIL INDICATES UNIT SUPPORT FROM THE |
| | BOTTOM OF THE BAR JOIST.PROVIDE A |
| | LETTER FROM THE STRUCTURAL ENGINEER |
| | INDICATING THAT JOIST IS DESIGNED FOR |
| | THIS APPLICATION FOR EQUIPMENT, PIPING |
| | DUCTS, ETC.. |
| | |
| | 5.PLAN SHEET M7.2 AUXILIARY DRAIN |
| | NOTE |
| | REFERENCES PLUMBING PLANS.PLAN SHEET |
| | P2.1 ONLY INDICATES THE PRIMARY DRAIN. |
| | PER 2001 FBC(M)307.2.3, AUXILIARY DRAIN |
| | IS TO TERMINATE AT A CONSPICUOUS POINT |
| | TO SERVE AS AN ALARM.PLEASE CLARIFY |
| | TERMINATION. |
| | |
| | 6.PLAN SHEET E3.3 ROOM 152 SHOWS UPS |
| | BATTERY ROOM.PROVIDE NUMBER OF |
| | BATTERIES TO BE STORED IN THIS AREA. |
| | SHOW COMPLIANCE WITH 2002 NEC 480.9 |
| | THROUGH 480.10. |
| | |
| | 7.PLAN SHEET E3.3 INDICATES RAISED |
| | FLOOR.PLEASE CLARIFY PURPOSE AND WILL |
| | THIS AREA BE VENTED? |
| | |
| | PLEASE NOTE, ADDITIONAL COMMENTS MAY |
| | FOLLOW PENDING RESPONSE TO REVIEW |
| | COMMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |