| Plan Review Notes For Permit 04111389 |
| Permit Number |
04111389 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-28 00:00:00 | FIRE REVIEW | | | | | | 1) BUILDING ADDRESS REQUIRED. A MINIMUM | | | OF AT LEAST 6" HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 2) PLEASE REF NFPA 101 LIFE SAFETY CODE | | | 2000 EDITION CHAPTER 38.3.3.2 INTERIOR | | | WALL AND CEILING FINISH. | | | | | | 3) PLEASE INDICATE THE LOCATION OF FIRE | | | EXTINGUISHERS ON FLOOR PLAN. (COULD NOT | | | LOCATE) | | | | | | 4) SHEET FA0.1 NOTE #17, SHOULD READ | | | HVAC DUCT SMOKE DETECTORS SHALL BE | | | CONNECTED TO THE FIRE ALARM CONTROL | | | PANEL AND INITIATE A GENERAL FIRE ALARM | | | NOT A SUPERVISORY. | | | | | | 5) THE FIRE ALARM SYSTEM SHALL BE | | | MONITORED BY A LICENSE UL LISTED FIRE | | | ALARM COMPANY FOR CENTRAL STATION | | | SERVICE. | | | | | | 6) SEPARATE SHOP DRAWINGS AND PERMIT | | | APPLICATION ARE REQUIRED FOR FIRE ALARM | | | AND FIRE SPRINKLER SYSTEMS REMODEL. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|