| 2004-12-15 00:00:00 | ************ UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SUBMIT MANUFACTURE SPECS |
| | FOR GENERATOR, ATS, AND FUEL TANKS. |
| | |
| | 2)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH SUBMITTED PANEL |
| | SCHEDULE. |
| | PLEASE SEE THERE ARE SOME MISSING. |
| | PLEASE SEE 700.12E FOR CIRCUITING EM/EXT |
| | LTS. |
| | |
| | |
| | 3)NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 4)NOTE: PLEASE SEE 110.26 FOR ELECTRICAL |
| | RM CLERENCE. (153) |
| | PLEASE IDENTIFY PANELS ON PLANS, ELECT |
| | RM. |
| | |
| | 5)NOTE: PLEASE SEE MAIN FOR GENERATOR IS |
| | SHOWN IN TENANT SPACE AND NOT GROUPED OR |
| | IN CLOSE PROXIMITY OF MAIN ELECTRICAL |
| | ROOM OR OTHER MAINS. |
| | PLEASE PROVIDE MORE INFORMATION ON |
| | THIS. |
| | 230.72,230.76,230.79. |
| | |
| | 6)NOTE: PLEASE SEE 700.7D, 230.95,240.13 |
| | FOR GROUND FAULT REQUIRED ON GENERATOR |
| | ALSO. |
| | IT IS NOTED FOR DP BUT NOT FOR MAIN 1 OF |
| | 2? OR GEN MAIN? |
| | |
| | 7)NOTE: PLEASE SHOW TRANSFORMER |
| | GROUNDING PER 250.30. |
| | |
| | 8)NOTE: PLEASE CLARIFY RMS 168,169, |
| | APPEAR TO BE SHOWN AS ONLY "SHOWERS"?? |
| | ARE THESE ALSO BATH RMS? |
| | |
| | 9)NOTE: PLEASE ALSO SUBMIT SPECS ON UPS |
| | SYSTEM. |
| | MUST SHOW A LISTING FROM A NRTL. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |