| Plan Review Notes For Permit 04111278 |
| Permit Number |
04111278 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-05-18 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. THE REDLINED ITEMS ON FROM THE | | | PRIOR REVIEW WERE NOT CORRECTED. | | | | | | 1} THE OCP AND FEEDERS FOR " NEW | | | SUBPANEL" ARE NOT LISTED IN THE | | | ORIGINATING PANEL("B"). | | | | | | 2} THE PANEL SCHEDULE SHOWS 100AMP MAINS | | | IN THE "SUB-PANEL". THE RISER SHOWS #6 | | | FEEDER CONDUCTORS, SEE 310.16. PLEASE | | | CORRELATE. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|