| 2005-04-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR (NOTE: DADE COUNTY NOA |
| | ALONE IS NOT AUTOMATICALLY A FL.PRODUCT |
| | APPROVAL. STILL NEEDS FLORIDA PRODUCT |
| | APPROVAL OR APPLY FOR LOCAL PRODUCT |
| | APPROVAL AS REQ'D BY RULE 9B-72): |
| | A) FIXED WINDOWS. PROVIDE FLORIDA COVER |
| | PAGE OR APPLY FOR LOCAL PRODUCT |
| | APPROVAL. |
| | **NOTE: ALSO, NEED PRODUCT APPROVAL FOR |
| | 72"X72" FIXED WINDOW. DADE COUNTY NOA |
| | SUBMITTED DOESN'T COVER THIS SIZE. |
| | |
| | B) SLIDING GLASS DOOR. NEED FLORIDA |
| | APPROVAL OR APPLY FOR LOCAL APPROVAL. |
| | |
| | C) TRUSS CONNECTORS SPECIFIED ON PLANS. |
| | |
| | D) CASEMENT WINDOWS ASSEMBLIES WITH |
| | WINDOWS TALLER THAN 63" TO MATCH THOSE |
| | SPECIFIED ON PLANS. PRODUCT APPROVAL |
| | SUBMITTED ONLY COVERS ASSEMBLIES UP TO |
| | 63" HIGH. ALSO, PROVIDE FLORIDA APPROVAL |
| | OR APPLY FOR LOCAL APPROVAL. |
| | |
| | 2- UPDATE TRUSS ANCHOR SCHEDULE. SEE USP |
| | OR SIMPSON LATEST CATALOGUEFOR TYPE |
| | AND NUMBER OF NAILS TO BE USED THAT WERE |
| | REVISED TO COMPLY WITH SEC. 1609.4.3 FBC |
| | 2001. ALSO, CHECK UPLIFT VALUES SHOWN ON |
| | CATALOGUE. OTHERWISE, PROVIDE COMPLETE |
| | ENGINEERING ANALYSIS THAT COMPLY WITH |
| | SEC. 1609.4.3 FBC WHEN TYPE AND NUMBER |
| | OF NAILS DON'T MATCH THOSE TESTED AND |
| | PUBLISHED BY THE MANUFACTURER. |
| | |
| | 3- ENERGY CALCULATIONS STILL SHOW UNDER |
| | ATTIC AREA WITHOUT BEING REVISED TO |
| | COMPLY WITH SEC. 604.1.A.1 CHAPTER 13 |
| | FBC 2001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |