 PROVISO
 ~~~~~~~
  
 1} PROVIDE 60AMP OCP IN PANEL "B" TO
 PROTECT #6 FEEDERS TO NEW SUB PANEL.
  
 2} RECEPTACLE IN THE LAUNDRY ROOM WITHIN
 6' OF SINK TO BE GFI.
  
 3} PENINSULAR RECEPTACLE REQUIRED PER
 210.52(C)(3)
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW