| Plan Review Notes For Permit 04111262 |
| Permit Number |
04111262 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-20 00:00:00 | ****** UNSAT ****** | | | | | | 1)NOTE: PLEASE SEE ALL NEW CIRCUITING | | | FOR BATH GFI RECEPTS. THESE MUST BE 20A | | | AND #12. 210.52D,210.11C3 | | | | | | 2)NOTE: PLEASE SEE A MIN OF 1.5KW | | | REQUIRED FOR LAUNDRY/WASHER CIRCUIT. | | | 220.16 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|