| Plan Review Notes For Permit 04111262 |
| Permit Number |
04111262 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-23 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT D1 SANITARY RISER DIAGRAM. THIS | | | IS A SOVENT SYSTEM AND AS SUCH IS AN | | | ENGINEERED SYSTEM. THE STACK THAT THE | | | NEW BATHROOM IS BEING TIED INTO SHALL BE | | | SHOWN AS EXISTING. SHOW WHERE THE NEW | | | BATHROOM IS CONNECTED TO THE SOVENT | | | STACK. INDICATE THE DEVELOPED LENGTH OF | | | THE PIPING FROM THE STACK TO THE | | | FIXTURES. SHOW THE AERATOR AND IF THERE | | | IS AN OFFSET THE DEAERATOR REQUIRED FOR | | | THIS ADDED BATHROOM. SECTION 104.2.1 | | | 2) SUBMIT A WATER RISER DIAGRAM SHOW THE | | | CONNECTION TO THE EXISTING WATER IN THE | | | UNIT AND ALL PIPE SIZES, WATER HAMMER | | | ARRESTORS ECT. SECTION 104.3.1.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|