| Plan Review Notes For Permit 04111257 |
| Permit Number |
04111257 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-30 00:00:00 | | | | | | | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5. | | | | | | PLANS MUST HAVE DESIGNER OF RECORD PRINT | | | NAME & SIGN PLANS PER 104.2.1, F.B.C. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|