Plan Review Notes
Plan Review Notes For Permit 04111230
Permit Number 04111230
Review Stop B
Sequence Number 4
Notes
Date Text
2004-12-09 00:00:00***CORRECTIONS***
  
 1.)REVISE VALUE TO INCLUDE NEW
 SHEATHING
  
 2.)APPLY FOR SEPARATE PERMITS FOR ALL
 BUILDINGS
  
 3.)SEE ATTACHED AMENDMENTS TO THE
 FBC2307.6B.HAVE ENGINEER PROVIDE A
 SPECIFICATION FOR REPAIR THAT IS CODE
 COMPLIANT.REPAIRS PROPOSED BY
 CONTRACTOR, 7/16 OSB OR 15/32 CDX DO NOT
 MEET MINIMUM ROOF SHEATHING CRITERIA.
 TRUSS SPACING NOT ADDRESSED IN
 ENGINEERING.
  
  