2004-12-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.) THE ENGINEER'S SPECIFICATION
 (INSTALLATION OVER 1/4" PLYWOOD DECK)
 CONFLICTS WITH THE PRODUCT APPROVAL,
 DECK DESCRIPTION, RE-ROOF 15/32"
 PLYWOOD
 MINIMUM.PROVIDE DESIGN INFORMATION AS
 TO HOW THIS SPECIFICATION IS CODE
 COMPLIANT IN REGARDS TO WIND LOADS.
  
 2.)CONVERSATIONS WITH THE CONTRACTOR
 IN REGARDS TO INSTALLATION METHODS
 CONFLICT WITH THE ENGINEER'S
 SPECIFICATION.CODE ISSUES WITH
 ALTERNATE INSTALLATIONS HAVE NOT BEEN
 ADDRESSED.
  
 ***NO RESUB FEE***
  