Date Text
2005-03-04 00:00:00DENIED
  
 1) ON SHEET S4 MARK J SPECIFIES A
 SIMPSON HDSA HOLD DOWN CONNECTOR.
 SHOULDN'T THIS BE A HD5A. PLEASE
 CORRECT.
  
 2) THE GR3 GIRDER IS SHOWN AS A 2PLY ON
 THE TRUSS DRAWINGS AND THE PLANS SPECIFY
 A 4PLY. PLEASE CORRECT.
  
 3) SPECIFY THE CONNECTIONS AT EACH END
 OF THE GR2 GIRDERS.
  
 4) SPECIFY THE CONNECTIONS FOR BOTH ENDS
 OF THE GR3 GIRDERS.
  
 5)THE UPLIFT FOR THE MG1 GIRDERS AT THE
 EXTERIOR WALL EXCEEDS THE UPLIFT
 SPECIFIED IN THE TRUSS SCHEDULE FOR THE
 MARK F CONNECTOR.
  
 6) THE TRUSS LAYOUT AND ROOF FRAMING
 PLAN ON S4 SPECIFIES OPENINGS IN THE
 ROOF TRUSSES FOR A/C, HOWEVER THERE IS
 NOTHING INDICATED ON THE ELEVATIONS OR
 THE BUILDING ROOF PLAN ON A6 AT THESE
 AREAS. PLEASE CLARIFY.
  
 7) THE NOAS FOR THE GLASS BLOCK WERE NOT
 SUBMITTED. I HAVE ATTACHED ONE COPY FOR
 YOU.
  
 8) SUBMIT THE INSTALLATION DRAWINGS/
 INSTRUCTIONS AND LIMITATIONS FOR THE UL
 CERTIFICATIONFOR THE OWENS CORNING
 SHINGLES. NOTE: MIAMI-DADE NOAS LIMIT
 INSTALLATION TO STRUCTURES WITH A MEAN
 ROOF HEIGHT OF 33 FEET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  