| Plan Review Notes For Permit 04111224 |
| Permit Number |
04111224 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-03-04 00:00:00 | DENIED | | | | | | 1) ON SHEET S4 MARK J SPECIFIES A | | | SIMPSON HDSA HOLD DOWN CONNECTOR. | | | SHOULDN'T THIS BE A HD5A. PLEASE | | | CORRECT. | | | | | | 2) THE GR3 GIRDER IS SHOWN AS A 2PLY ON | | | THE TRUSS DRAWINGS AND THE PLANS SPECIFY | | | A 4PLY. PLEASE CORRECT. | | | | | | 3) SPECIFY THE CONNECTIONS AT EACH END | | | OF THE GR2 GIRDERS. | | | | | | 4) SPECIFY THE CONNECTIONS FOR BOTH ENDS | | | OF THE GR3 GIRDERS. | | | | | | 5)THE UPLIFT FOR THE MG1 GIRDERS AT THE | | | EXTERIOR WALL EXCEEDS THE UPLIFT | | | SPECIFIED IN THE TRUSS SCHEDULE FOR THE | | | MARK F CONNECTOR. | | | | | | 6) THE TRUSS LAYOUT AND ROOF FRAMING | | | PLAN ON S4 SPECIFIES OPENINGS IN THE | | | ROOF TRUSSES FOR A/C, HOWEVER THERE IS | | | NOTHING INDICATED ON THE ELEVATIONS OR | | | THE BUILDING ROOF PLAN ON A6 AT THESE | | | AREAS. PLEASE CLARIFY. | | | | | | 7) THE NOAS FOR THE GLASS BLOCK WERE NOT | | | SUBMITTED. I HAVE ATTACHED ONE COPY FOR | | | YOU. | | | | | | 8) SUBMIT THE INSTALLATION DRAWINGS/ | | | INSTRUCTIONS AND LIMITATIONS FOR THE UL | | | CERTIFICATIONFOR THE OWENS CORNING | | | SHINGLES. NOTE: MIAMI-DADE NOAS LIMIT | | | INSTALLATION TO STRUCTURES WITH A MEAN | | | ROOF HEIGHT OF 33 FEET. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|