| 2004-12-21 00:00:00 | DENIED |
| | |
| | 1) THE OWNER/AGENT IS REQUIRED TO SIGN |
| | THE ENERGY CALC. FORMS. THE ENERGY |
| | CALCS.DO NOT SPECIFY THE 2X6 WOOD FRAME |
| | EXTERIOR WALLS WITH R-19 INSULATION. THE |
| | WALLS ADJACENT TO THE GARAGE ARE |
| | SPECIFIED WITH R-19 INSULATION ON THE |
| | PLAN AND R-11 ON THE ENERGY CALCS. |
| | |
| | 2) FBC 2504.2.1 REQUIRES EXTERIOR |
| | APPLICATIONS OF PORTLAND CEMENT PLASTER |
| | TO COMPLY WITH ASTM C 92. THIS STANDARD |
| | REQUIRES PLASTER OVER METAL BASE TO BE |
| | 5/8" THICK WHEN APPLIED HORIZONTALLY AND |
| | 7/8" THICK WHEN APPLIED VERTICALLY. |
| | |
| | 3) THE MEAN ROOF HEIGHT FOR THE |
| | STRUCTURE IS 38'-5" SUBMIT ENGINEERED |
| | CALCULATIONS FOR THE ROOF SHEATHING |
| | FASTENING REQUIREMENTS. |
| | |
| | 4) THEIR IS A TYPO ON SHEET A12. THE |
| | TEXT IS PRINTED OVER. |
| | |
| | 5) THE STRUCTURAL NOTES ON S5 HAS A TYPO |
| | THAT REFERS TO THE FBC N1 EDITION. |
| | |
| | 6) SPECIFY THE REQUIRED SOIL BEARING |
| | CAPACITY FOR THE STRUCTURE ON THE |
| | PLANS. |
| | |
| | 7) SUBMIT A SIGNED AND SEALED COPY OF |
| | THE SOIL REPORT. |
| | |
| | 8) THE POSITIVE PRESSURES LISTED IN THE |
| | DOOR AND WINDOW WIND PRESSURE TABLE ON |
| | S5 DO NOT APPEAR TO HAVE BEEN ADJUSTED |
| | FOR HEIGHT BY MULTIPLYING BY THE |
| | APPROPRIATE COEFFICENT. SEE FBC TABLE |
| | 1606.2D FOR M.R.H. OF 38'-5". |
| | |
| | 9) PROVIDE CAP DETAILS FOR THE (WP-1) |
| | 4X4 WOOD COLUMN AND THE (SC-1) STEEL |
| | COLUMN. |
| | |
| | 10) DETAIL 5 ON S7 SHOWS A 6X6 WOOD POST |
| | CAP WHICH IS NOT CALLED OUT ON THE |
| | PLANS. PLEASE CLARIFY. |
| | |
| | 11) SUBMIT PRODUCT APPROVALS FOR ASPHALT |
| | ROOF SHINGLES THAT WERE TESTED TO ASTM D |
| | 3161M OR PA 107 AND ARE NOT LIMITED TO A |
| | 33' M.R.H. |
| | |
| | 12) THE DOOR SCHEDULE FOR UNIT 2 AND 2R |
| | DOES NOT LIST THE 16' WIDE OVERHEAD |
| | GARAGE DOOR OR THEIR WIND PRESSURES. |
| | |
| | 13) THE NOA/ELEVATION REPORT FOR THE |
| | GLASS BLOCK IS MISSING. |
| | |
| | 14) A PRODUCT APPROVAL FOR FIXED GLASS |
| | WINDOWS WAS SUBMITTED, HOWEVER, THERE |
| | AREN'T ANY SPECIFIED ON THE PLANS. |
| | PLEASE CLARIFY. |
| | |
| | 15) THE TRUSS LAYOUTS AND DRAWINGS ARE |
| | REQUIRED TO HAVE THE ORIGINAL WET |
| | SIGNATURE OF THE TRUSS ENGINEER PER FAC |
| | 61G15-23.002. |
| | |
| | 16) THE ROOF PLAN ON S4 DOES NOT MATCH |
| | THE TRUSS LAYOUT. PLEASE REVISE. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |