| 2004-12-27 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) PLANS SHALL BE ROUTED TO FDBR, |
| | DIVISION OF BUSINESS REGULATION, HOTEL |
| | AND RESTURANT DIVISION FOR REVIEW. |
| | RESUBMIT WITH EACH SET OF PLANS STAMPED |
| | AND WORKSHEETS ATTACHED. SECTION |
| | 101.4.7 |
| | 2) GREASE INTERCEPTORS SHALL BE SIZED BY |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE |
| | PER WASTE ORD. #2938-96. CONTACT MR. |
| | COMPO AT (561) 837-4074 OR FAX # (561) |
| | 659-7458. SUBMIT WORKSHEET FROM MR. |
| | COMPO WITH PLANS WHEN RESUBMITTING. |
| | 3) ALL SHEETS - SIGNATURE REQUIRED ON |
| | SEAL PER FAC 61G1-16.003, |
| | 61G15-23.002(1)(2) & FS 481.219, |
| | 471.025. INITIALS ARE NOT APPROVED. FULL |
| | FIRST AND LAST NAME REQUIRED ON THE |
| | SIGNATURE. |
| | 4) SHTS 1, 2, & 3 OF 3 STATES PALM BEACH |
| | COUNTY WATER UTILITIES DEPARTMENT. PLANS |
| | ARE SUBMITTED TO "CITY OF WEST PALM |
| | BEACH". CHANGE DETAILS TO APPROVED |
| | DETAILS FOR THE CITY. SECTION 104.2.1 |
| | 5) SHTS 1, 2, & 3 OF 3 NO TITLE BLOCKS |
| | FOR SIGNED, SEALED, DATED PLANS AS |
| | REQUIRED BY FAC 61G1-16.004, |
| | 61G15-23.002(2). PLEASE SEE ALL |
| | INFORMATION REQUIRED TO BE IN TITLE |
| | BLOCK. FS 481.2055, 471.025. |
| | 6) ALL SHEETS, TITLE BLOCK REQUIRES A |
| | CERTIFICATE OF AUTHROIZATION PER FAC |
| | 61G15-23.002, FAC 61G1-16.004 & FS |
| | 481.219, 471.025. |
| | 7) SHT L-2 TO BE SIGNED,SEALED,DATED AND |
| | ALL TITLE BLOCK INFORMATION. THIS SHEET |
| | CALLS FOR A PUMP/LAKE SUPPLY, BUT SHT |
| | C-3 INDICATES A METER AND BACKFLOW FOR |
| | IRRIGATION. PLEASE CLARIFY. SEC |
| | 104.2.1. |
| | 8) SHT C-5 DUMPSTER FLOOR DRAIN |
| | INDICATES CONNECTION TO GREASE SYSTEM. |
| | STORM WATER SHALL NOT DRAIN INTO THE |
| | GREASE WASTE SYSTEM. PLEASE INDICATE IF |
| | THE DUMPSTER PAD WILL BE COVERED. |
| | SECTION 104.2.1 & CITY CODE SECTION |
| | 90-125(5). |
| | 9) SHT P-1 STORM DRAIN RISER DIAGRAM. |
| | HORIZONTAL DRAINAGE PIPING SHALL BE |
| | INSTALLED IN UNIFORM ALIGNMENT AR |
| | UNIFORM SLOPES. PIPING FROM 1ST ROOF |
| | DRAIN IS SHOWN AT 1/4"FT AND PIPING |
| | DOWNSTREAM OF 2ND ROOF DRAIN IS SHOWN AT |
| | 1/2"FT. THE PIPING SHALL BE UNIFORM IN |
| | SLOPE. SECTION 704.1. |
| | 10) SHT P-1 CONDENSATE LINES TO FLOOR |
| | DRAIN #2. FLOOR DRAINS ARE NOT APPROVED |
| | AS AN INDIRECT WASTE RECEPTOR. SAFE |
| | WASTES ARE NOT APPROVED. EITHER A FLOOR |
| | SINK OR A HUB DRAIN ARE APPROVED PER |
| | SECTION 802.3OR 802.3.2. - INDIRECT |
| | WASTE RECEPTORS SHALL BE LOCATED SO AS |
| | NOT TO CREATE A TRIPPING HAZARD. |
| | 11) SHT P-1 DETAIL 3/P-1 AND SANT. RISER |
| | DIAGRAM SHOW A 2" VENT FOR THE LAV IN |
| | THE WOMENS TOILET ROOM, BUT SANT. PIPING |
| | PLAN SHOWS A 3" VENT. PLEASE CORRELATE |
| | PLANS TO SHOW THE SAME INFORMATION. |
| | SECTION 104.2.1. |
| | 12) SHT P-2 WATER RISER DIAGRAM SHOWS |
| | VACUUM BREAKERS AT EACH FIXTURE. (SEE |
| | SHT P-3 PLUMBING LEGEND). PLEASE |
| | CLARIFY. (INFORMATIONAL) AIR CHAMBERS |
| | ARE NOT APPROVED. WATER HAMMER ARRESTORS |
| | REQUIRED BY SECTION 604.9 AT QUICK |
| | CLOSING VALVES ONLY. - SECTION 606.1(4) |
| | FULL OPEN VALVES ARE REQUIRED ON THE TOP |
| | OF EVERY WATER DOWN-FEED PIPE. |
| | 13) SHT P-2 WATER FILTER UNITS MUST MEET |
| | THE REQUIREMENTS OF NSF-42. SECTION |
| | 611.1. SUBMIT MANUF. SPECIFICATION |
| | SHEETS. |
| | 14) SHT P-2 THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR GAS PLANS/PERMIT: |
| | A. TYPE OF GAS, (LP OR NATURAL) |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | C. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE SECTION 304. |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | G. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | H. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | I. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 15) SHT P-4 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL IS REQUIRED PER |
| | SECTION 607.3.2 |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |