| 2004-12-29 00:00:00 | PROVISO:PLAN CHECK | | | ADDITIONAL PERMITS REQUIRED FOR HOOD, | | | FIRE SUPPRESSION, WALK-IN COOLERS, AND | | | GAS.PLEASE PROVIDE MANUFACTURER | | | SUBMITTAL DATA AND CUT SHEETS FOR THE | | | WALK-IN COOLER/FREEZER WITH PERMIT | | | APPLICATION. | | | | | | WELDS ARE TO BE INSPECTED PRIOR TO | | | COVERING WITH THE UNIFRAX-FIRE WRAP | | | INDICATED ON PLAN SHEET H-1. | | | | | | PLEASE REFERENCE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS FOR THE | | | PROTECTION FROM UV RAYS TO THE PVC | | | CONDENSATE LOCATED ON THE ROOF. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|