| 2004-12-03 00:00:00 | ************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS AS REQUIRED UNDER FAC |
| | 61G15-23.002,61G1-16.004. |
| | FS 471.023,481.219 |
| | PLEASE SEE ALL SHEETS AND FOR ALL TRADES |
| | WHEATHER OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | **NOTE** ELECTRICAL ENGINEERS TITLE |
| | BLOCK IS CORRECT. |
| | |
| | 2)NOTE: PLEASE SUBMIT WIND LOADING |
| | CALCUALTIONS FOR SITE LT POLES FOR BLDG |
| | REVIEW. MUST ALSO BE NOTED ON ELECTRICAL |
| | PLANS FOR REQUIREMENTS OF FBC 140 MPH |
| | WIND S. |
| | |
| | 3)NOTE: PLEASE SEE "SHOW WINDOW" RECEPTS |
| | WILL BE REQUIRED FOR WINDOW AREAS. |
| | PLEASE SEE 210.62 |
| | AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED DIRECTLY ABOVE A SHOW WINDOW |
| | FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR |
| | FRACTION THEREOF OF SHOW WINDOW AREA |
| | MEASURED HORIZONTALLY AT ITS MAXIMUM |
| | WIDTH. |
| | |
| | 4)NOTE: PLEASE SEE MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM MAIN |
| | DISCONNECT TO PANLE DP AND FROM DP TO |
| | SUB-PANELS.EXPOSED NON?CURRENT-CARRYING |
| | METAL PARTS OF FIXED EQUIPMENT LIKELY TO |
| | BECOME ENERGIZED SHALL BE GROUNDED. |
| | PLEASE ALSO SEE LOCAL AMENDMENTS WHICH |
| | REQUIRE AN EQUIPMENT GRND PULLED WITH |
| | OUTSIDE CONDUITS EVEN IF EMT. |
| | 250.110,250.122 |
| | |
| | 5)NOTE: PLEASE SEE CORD AND PLUG |
| | CONNECT-ED EQUIPMENT ABOVE CEILINGS AND |
| | RECEPTS ABOVE CEILINGS NOT PERMITTED. |
| | |
| | |
| | 6)NOTE: PLEASE PROVIDE A NOTE ON PLANS |
| | FOR REQUIREMENTS OF GFI PROTECTION IN |
| | KITCHEN FOR ALL RECEPTS. |
| | LL 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE |
| | LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | ALL 125-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE RECEPTACLES INSTALLED IN THE |
| | LOCATIONS SPECIFIED IN (1), (2), AND (3) |
| | SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL:SECTION 210.8(B)(3) IS NEW |
| | FOR THE 2002 CODE AND REQUIRES ALL 15- |
| | AND 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NONDWELLING-TYPE KITCHENS TO BE GFCI |
| | PROTECTED. THIS REQUIREMENT APPLIES TO |
| | EACH AND EVERY 15- AND 20-AMPERE, |
| | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| | NOT THE RECEPTACLE SERVES COUNTERTOP |
| | APPLIANCES. |
| | 210.8B3 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETED SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE ANY POSSIBLE REVIEW COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY OR MAY |
| | NOT AFFECT ELECTRICAL PLANS. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |