| 2004-12-23 00:00:00 | ****CORRECTIONS**** |
| | PAID PLAN REVIEW |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY BEFORE A PERMIT CAN BE |
| | ISSUED.THE PLANS MUST BE STAMPED AND |
| | THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | 233-5025 |
| | |
| | 3.)STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO TEST REPORTS |
| | FAC9B-72.WWW.FLORIDABUILDING.ORG |
| | |
| | 4.)THE SURVEY SHOWS ONE PARCEL, |
| | PROPERTY APPRAISER'S SHOWS TWO. HAS A |
| | UNITY OF TITLE BEEN FILED TO JOIN THE |
| | TWO PARCELS?IF IT HAS, PLEASE PROVIDE |
| | EITHER A RECORDED COPY OR SUPPLY THE |
| | BOOK/PAGE. THE IMPROVEMENTS CROSS OVER |
| | THE PROPERTY LINE.PLEASE ADDRESS. |
| | |
| | 5.)NOTE -THIS PROPERTY IS LOCATED |
| | IN |
| | A FLOOD ZONE.A FORM BOARD ELEVATION |
| | CERTIFICATE WILL BE REQUIRED BEFORE |
| | CONCRETE POUR. |
| | |
| | 6.)SHEET C4, HANDICAP PARKING IS TO |
| | COMPLY WITH CITY OF WEST PALM BEACH |
| | REQUIREMENTS, SEE ATTACHED. |
| | |
| | 7.)PRIOR TO PERMITTING, PLEASE |
| | PROVIDE |
| | A SOILS INVESTIGATION REPORT. |
| | |
| | 8.)THE NOTE REGARDING STORM SHUTTERS |
| | ON SHEET A14 IS INCORRECT.IMPACT |
| | PROTECTION REQUIRED IN WINDBORNE DEBRIS |
| | REGIONS, FBC1606.1.4. |
| | |
| | 9.)STUCCO OVER WIRE LATH IN A |
| | VERTICAL |
| | APPLICATION IS TO BE A MINIMUM OF 7/8", |
| | FBC2504.2.2, ASTM C926.REVISE DETAILS |
| | 1-A11, 7-A2.1, ANY OTHER AFFECTED |
| | DETAILS. |
| | |
| | 10.)INDICATE THE INSTALLATION METHOD |
| | IN THE NOA FOR THE MODIFIED ROOF.NOT |
| | ALL METHODS ARE COMPLIANT WITH THE |
| | DESIGN PRESSURE SPECIFIED.SHEETS |
| | WHICH |
| | ARE NOT APPLICABLE TO THIS APPLICATION |
| | MAY BE DISCARDED. |
| | |
| | 11.) STOREFRONT NOTES, ITEM #6, STATES |
| | THAT PALM BEACH COUNTY IS IN THE HIGH |
| | VELOCITY HURRICANE ZONE.PALM BEACH |
| | COUNTY IS NOT IN THE HIGH VELOCITY |
| | ZONE. |
| | PLEASE MODIFY THE NOTE TO MAKE CLEAR |
| | THE |
| | SPECIFICATION FOR THE STOREFRONT |
| | OPTION. |
| | TEST REPORTS AND PRODUCT APPROVALS ARE |
| | STILL REQUIRED OUTSIDE OF THE HVHZ, |
| | FBC1707.4, 1707.3. |
| | |
| | 12.)THE NOA FOR THE NARROW STILE DOOR |
| | IS LIMITED TO 3'0 PER LEAF; SHEET A16, |
| | DOOR SCHEDULE, #1, SHOWS A DIMENSION OF |
| | 3'6".IS THIS THE SAME DOOR? |
| | |
| | 13.)DETAIL 5-S2 AND THE WOOD TRUSS |
| | TIE |
| | DOWN SCHEDULE REFER TO A HUGHES |
| | CONNECTOR.THIS COMPANY HAS BEEN OUT |
| | OF |
| | BUSINESS FOR SEVERAL YEARS; PLEASE |
| | REVISE THE CONNECTOR TO ONE THAT IS |
| | AVAILABLE.CHECK ALL DETAILS. |
| | |
| | 14.)THE FASTENING FOR USP TAPL16 |
| | (4-S2, WOOD TRUSS TIE DOWN SCHEDULE) |
| | CONFLICTS WITH THE CATALOG (SPECIFIES |
| | 11 |
| | NAILS RATHER THAN 13).REVISE AND |
| | CHECK |
| | ALL OTHER FASTENING SPECIFICATIONS. |
| | |
| | 15.)3-S3 SHOWS A FRAME WALL ENCLOSING |
| | THE ATTIC SPACE.TYPE V CONSTRUCTION |
| | IS |
| | TO BE NONCOMBUSTIBLE EXTERIOR WALLS, |
| | FBC607. |
| | |
| | 16.)SEPARATE PERMIT REQUIRED FOR |
| | DUMPSTER ENCLOSURE. |
| | |
| | |