| 2006-01-20 00:00:00 | REDLINED PLANS. | | | | | | GEC HAS BEEN CHANGED TO A #4 WHEN A MIN | | | OF #2 AWG IS REQUIRED BASED ON | | | 250.66,310.15B6 | | | | | | ** PLEASE KNOW, ORIG PLANS AND ALL | | | REVISIONS THROUGH REV #10 SHOWED 1/0 AWG | | | , 2-COPPER GRND RODS, CWP AND FOOTER | | | STEEL BOND WITH #4. |
|