Plan Review Notes
Plan Review Notes For Permit 04111097
Permit Number 04111097
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-23 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES ALL PLANS TO HAVE PRINTED NAME
 AND SIGNATURE OF PERSON RESPONSIBLE FOR
 PLANS.
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 REQUIRED TITLE BLOCK AND MISSING
 INFORMATION FOR PLANS SIGNED BY AN
 ENGINEER.
 FS 471.025, 471.023.
 PLEASE ALSO SEE PLANS ARE REQUIRED TO BE
 SIGNED WITH LEGAL SIGNATURE, IF THIS IS
 LEGAL SIAGNATURE AND NOT INITIALS,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED NOTORIZED LETTER PERTAINING TO
 LEGAL "SIG".
  
 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR VALUATION OF PERMIT APPLICATION FOR
 SCOPE OF WORK.
 FBC 104.6.5
  
 4)NOTE: PLEASE SEE ELECTRICAL PLANS
 REFERENCT THE SFBC, WHICH IS NOT IN
 EFFECT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  