Plan Review Notes
Plan Review Notes For Permit 04111095
Permit Number 04111095
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-03 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. SECTION 104.2.1. NO
 SIGNATURE ON DRAWINGS.
 2) PIPING SHALL NOT BE INSTALLED IN
 SOLID FLOOR SLABS, SUCH AS CONCRETE OR
 MASONRY, EXCEPT WHERE THE CODE OFFICIAL
 DETERMINES THAT THERE IS NO OTHER
 PRACTICAL MANNER OF INSTALLING SUCH
 PIPE. SINCE THIS IS NOT AN ISLAND RANGE,
 THE PIPING SHALL BE IN THE WALLS AND
 OVERHEAD. SECTION 404.6.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]