| 2004-12-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1) ALL DRAWINGS SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. SECTION 104.2.1. NO | | | SIGNATURE ON DRAWINGS. | | | 2) PIPING SHALL NOT BE INSTALLED IN | | | SOLID FLOOR SLABS, SUCH AS CONCRETE OR | | | MASONRY, EXCEPT WHERE THE CODE OFFICIAL | | | DETERMINES THAT THERE IS NO OTHER | | | PRACTICAL MANNER OF INSTALLING SUCH | | | PIPE. SINCE THIS IS NOT AN ISLAND RANGE, | | | THE PIPING SHALL BE IN THE WALLS AND | | | OVERHEAD. SECTION 404.6. | | | 3. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|