Plan Review Notes
Plan Review Notes For Permit 04111093
Permit Number 04111093
Review Stop M
Sequence Number 3
Notes
Date Text
2005-02-09 00:00:00PROVISO:
 1.PROVIDE REVISED OR AS-BUILT DRAWINGS
 INDICATING RETURN AIR FROM THE MASTER
 SUITE.SHOW COMPLIANCE WITH 2001 FBC(M)
 601.4 (SEE ATTACHED).PLEASE NOTE ALL
 AIR INTO THE MASTER SUITE IS TO BE
 INCLUDED FOR A TOTAL OF SUPPLY AIR INTO
 THAT AREA.THE RETURN AIR SHALL BE
 SIZED ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.