| Plan Review Notes For Permit 04111093 |
| Permit Number |
04111093 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-02-08 00:00:00 | DENIED: | | | PLEASE PROVIDE A COMPLETED FORM 600C FOR | | | THE ADDITION ONLY (PER 2001 FBC CHAPTER | | | 13 SUB SECTION 600). | | | | | | RETURN AIR REQUIRED FROM THE MASTER | | | SUITE, REFERENCE 2001 FBC(M)601.4 | | | EXCEPTIONS 1 THROUGH 3 FOR PROPER SIZING | | | OF THE RETURN AIR JUMPER. | | | | | | PLEASE PROVIDE INFORMATION ON THE | | | EXISTING EQUIPMENT.PROVIDE MAKE, | | | MODEL, AND BTU OF THE SYSTEM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|