| Plan Review Notes For Permit 04111093 |
| Permit Number |
04111093 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-07 00:00:00 | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE NEW BEDROOM NEEDS A RECEPTACLE | | | TO | | | COMPLY WITH 210.52(A)(2). | | | | | | 2} THE "GENERAL RECEPTACLE" CALCULATION | | | IS NOT NEEDED FOR A RESIDENTIAL | | | CALCULATION, ONLY COMMERCIAL. | | | | | | 3} PLEASE GIVE THE RATING OF THE | | | EXISTING SERVICE IN AMPS, THE | | | CALCULATION DID NOT INDICATE. | | | | | | 4} THE VALUE ON THE PERMIT IS INCORRECT | | | FOR THE SCOPE OF WORKAND DOES NOT | | | COMPLY WITH 104.6.5. INCREASE AND | | | CHANGE | | | ON THE APPLICATION. | | | | | | 5} THE ARCHITECT MUST SEAL, SIGN AND | | | DATE THE PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE | | | CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|