| 2009-04-21 10:17:35 | ** DENIED REVISIONS** |
| | |
| | |
| | |
| | 1) NOTE: ALL LOW VOLTAGE SYSTEMS NEED TO BE PERMITTED. |
| | ONLY SOME SYSTEM HAVE HAD PERMITS APPLIED. THERE ARE |
| | ALSO SOME PERMITS FROM PREVIOUS SYSTEMS WHICH WERE |
| | EXPIRED AND NEED TO BE RE-APPLIED. |
| | THESE PLANS MAY BE REFERENCED FOR A TURN AROUND |
| | PERMITS. HOWEVER VALUE FOR SCOPE OF WORK NEEDS TO BE |
| | VERIFIED ALONG WITH PERMIT VALUATION FEES. |
| | THE ACCESS CONTROL SYSTEM BEING PROPOSED NEEDS TO BE |
| | SUBMITTED UNDER SEPARATE PLANS AND PERMITS. |
| | FBC 105.1 |
| | |
| | 2) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE *DATA |
| | ROOM*. DOES THIS ROOM MEET 645.4 1-5?. IF NOT, PLEASE |
| | PLACE NOTE ON PLANS THAT *NOW WIRING METHODS IN NEC 645 |
| | ARE PERMITTED IN THIS ROOM*. |
| | IT IS RECOMMENDED TO VERIFY WITH ANY IT/MIS PERSONNEL |
| | FROM PBAC THAT WIRING METHODS IN NEC 645 ARE NOT TO BE |
| | USED. IF MEETING 645.4 THEN WIRING METHODS OF 645 ARE |
| | PERMITTED. IF NOT MEETING ALL OF 645.4, 1-5, THEN ALL |
| | WIRING METHODS IN CHAPTERS 1-4 ARE MANDATORY. |
| | |
| | |
| | 3) NOTE: PLEASE PROVIDE INFORMATION OF NEW SYSTEMS |
| | BEING INSTALLED FROM MANHOLE FOR LV DATA. IS THIS |
| | UTILITY ENTRANCE OR FROM A SYSTEM ON THE BASE BUILDING |
| | SITE. IF THIS IS FROM A UTILITY PLEASE SHOW HOW |
| | GROUNDING/BONDING OF SYSTEMS IS TAKING PLACE. 800.100, |
| | 250 |
| | |
| | |
| | |
| | |
| | |
| | NO FURTHER ELECTRICAL REVISIONS TO BE DONE UNTIL |
| | APPLICATIONS ARE MADE. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |