Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop E
Sequence Number 40
Notes
Date Text
2007-10-07 13:00:422007-10-07 13:00:42
  
 *** DENIED REVISION ***
  
 PHASE II/ ROTUNDA
  
 1) NOTE: PLEASE SEE THIS IS A THRESHOLD PROJECT AND
 THREE SETS OF PLANS ARE NEEDED.
 PLEASE SEE THAT THE ARCHITECTURAL AND OTHER TRADES WERE
 SPLIT UP HOWEVER THESE NEED TO BE SUBMITTED TOGETHER AS
 THE REVISIONS AS SUBMITTED CLEARLY AFFECT ALL TRADES
 FOR REVIEW.
  
 2) NOTE: PLEASE SEE THE ARCHITECT SEAL USED ON A SHEETS
 IS NO LONGER VALID FOR USE. PLEASE SEE FAC 61G1-16.002
 AS THE MINIMUM SIZE WAS CHANGED BY THE BOARD SEVERAL
 YEARS AGO.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE.
  
 3) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8
 AND 7.9 NEEDS TO BE MET.
 PLEASE SEE THERE ARE AREAS IN WHICH BATTERY BACK UP
 TYPE OF LIGHTING FIXTURES ARE MISSING.
 PLEASE KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS
 PATHS INCLUDING THAT TO THE EXIT DISCHARGE
 AREAS/PATHS.
 FOR EXAMPLE: PLEASE SEE THE STAIR AREAS OUTSIDE WHICH
 ARE PART OF THE EXIT DISCHARGE WHICH DO NOT CONTAIN
 BATTERY BACK UP LIGHTING.
 PLEASE SEE THE HALL WHICH DOES NOT INDICATE ANY
 EMERGENCY LIGHTING FIXTURES.
 PLEASE SEE COURTYARD AREAS AS THESE ARE EXIT PATHS
 HOWEVER AS THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF
 WAY OR SAFE DISTANCE FROM THE BUILDING, EMERGENCY
 LIGHTING FIXTURES WILL BE REQUIRED.
 PLEASE SEE ANY TOILETS WHICH ARE NOT A SINGLE POINT OF
 USE WILL ALSO REQUIRE A BATTERY BACK UP FIXTURES OF
 SOME TYPE.
 PLEASE SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL
 ARE LISTED.
 PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR
 ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE
 THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE
 MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC
 104.1.2, FAC 61G15-33.004
 NFPA-101 7.8, 7.9
  
 4) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 WHICH COORDINATE ALL LIGHTING ON PLANS AND FIXTURE
 LEGEND. PLEASE SEE THAT NO UPDATED CALCULATIONS WERE
 SUBMITTED BASED ON THE REVISED LIGHTING FIXTURES FROM
 PHASE ONE AND WILL BE REQUIRED BEFORE PHASE TWO
 CONSTRUCTION.
 THE INPUT DATA REPORT NEEDS ALL ITEMS ON PLANS WHICH
 CONSUME ENERGY AND PROVIDES EFFICIENCY TO BE ON THE
 IDR.
 PLEASE SEE 2001 FBC AND CHAPTER 13, 400.2, 400.3.A,
 415.1.AB.1, 415.1.A, TABLE 4-15, 415.2 ETC.
 PLEASE KNOW THE REVISED CALCULATIONS WILL BE REQUIRED
 TO BE DONE UNDER THE CODE IN AFFECT AND UNDER PERMIT
 APPLICATION.
  
  
 5) NOTE: PLEASE CLEARLY SEPARATE ELECTRICAL ON RISER
 FOR WHICH IS PART OF EACH PHASE AS THE PHASE I WORK IS
 COMPLETED.
 PLEASE SHOW HOW ALL NEW WORK WILL TAKE PLACE FOR
 INSTALLATION OF FEEDERS ETC TO EXISTING EQUIPMENT WHICH
 IS CURRENTLY ENERGIZED. THIS WAS GONE OVER SEVERAL
 YEARS AGO WHEN THIS PROJECT STARTED THAT THIS
 INFORMATION WOULD BE NEEDED AT A LATER DATE FOR PHASE
 II.
 FBC 104.1.2
 ** PLEASE SEE THAT REVISIONS ARE BEING SUBMITTED FOR
 SHEETS AND ITEMS WHICH HAVE ALREADY HAD A FINAL
 INSPECTION. PLEASE DO NOT SUBMIT ANY REVISIONS FOR WORK
 WHICH WAS ALREADY COMPLETED EXCEPT THAT WORK WHICH IS
 DIRECTLY AFFECTED BY PHASE II.
 FOR EXAMPLE: WHY ARE ALL VOLTAGES ON PANELS BEING NOTED
 AS REVISIONS?
 PLEASE KNOW THAT A DETAILED RESPONSE LETTER/REVISION
 LISTING LETTER WOULD HELP ON THE REVIEW PROCESS. (NOT
 REQUIRED HOWEVER REVISIONS AS SUBMITTED ARE CONFUSING
 AND SOME CHANGES MADE ARE NOT UNDERSTOOD)
 PLEASE PROVIDE MORE INFORMATION.
  
 6) NOTE: PLEASE SEE FBC CHAPTER 11 FOR ALL MINIMUM
 LEVELS FOR HORN/STROBE DEVICES. ALL LOCATIONS AND
 MINIMUM LEVELS SHALL BE SHOWN AND STATED. 11-4.28.1,.2
 AND .3(4).
 ** EVEN AS THE FA SYSTEM IS UNDER A SEPARATE PERMIT
 THESE ITEMS ARE STILL REQUIRED ON PLANS FOR MINIMUM ADA
 COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]