| | *** DENIED REVISION *** |
| | |
| | PHASE II/ ROTUNDA |
| | |
| | 1) NOTE: PLEASE SEE THIS IS A THRESHOLD PROJECT AND |
| | THREE SETS OF PLANS ARE NEEDED. |
| | PLEASE SEE THAT THE ARCHITECTURAL AND OTHER TRADES WERE |
| | SPLIT UP HOWEVER THESE NEED TO BE SUBMITTED TOGETHER AS |
| | THE REVISIONS AS SUBMITTED CLEARLY AFFECT ALL TRADES |
| | FOR REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE THE ARCHITECT SEAL USED ON A SHEETS |
| | IS NO LONGER VALID FOR USE. PLEASE SEE FAC 61G1-16.002 |
| | AS THE MINIMUM SIZE WAS CHANGED BY THE BOARD SEVERAL |
| | YEARS AGO. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY |
| | OTHER TRADE. |
| | |
| | 3) NOTE: PLEASE SEE THAT COMPLIANCE WITH NFPA-101 7.8 |
| | AND 7.9 NEEDS TO BE MET. |
| | PLEASE SEE THERE ARE AREAS IN WHICH BATTERY BACK UP |
| | TYPE OF LIGHTING FIXTURES ARE MISSING. |
| | PLEASE KNOW THAT LIGHTING IS REQUIRED FOR ALL EGRESS |
| | PATHS INCLUDING THAT TO THE EXIT DISCHARGE |
| | AREAS/PATHS. |
| | FOR EXAMPLE: PLEASE SEE THE STAIR AREAS OUTSIDE WHICH |
| | ARE PART OF THE EXIT DISCHARGE WHICH DO NOT CONTAIN |
| | BATTERY BACK UP LIGHTING. |
| | PLEASE SEE THE HALL WHICH DOES NOT INDICATE ANY |
| | EMERGENCY LIGHTING FIXTURES. |
| | PLEASE SEE COURTYARD AREAS AS THESE ARE EXIT PATHS |
| | HOWEVER AS THEY ARE NOT CONSIDERED THE PUBLIC RIGHT OF |
| | WAY OR SAFE DISTANCE FROM THE BUILDING, EMERGENCY |
| | LIGHTING FIXTURES WILL BE REQUIRED. |
| | PLEASE SEE ANY TOILETS WHICH ARE NOT A SINGLE POINT OF |
| | USE WILL ALSO REQUIRE A BATTERY BACK UP FIXTURES OF |
| | SOME TYPE. |
| | PLEASE SEE THERE ARE OTHER AREAS ALSO HOWEVER NOT ALL |
| | ARE LISTED. |
| | PLEASE SUBMIT AND PROVIDE LIGHTING PHOTO-METRICS FOR |
| | ALL EGRESS PATHS TO THE PUBLIC RIGHT OF WAY. PLEASE SEE |
| | THE LEVELS UNDER NORMAL FOR STAIRS SHALL MEET THE |
| | MINIMUM OF 10FT CANDLES PER 7.8.1.3 AND IS PERMITTED TO |
| | GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. FBC |
| | 104.1.2, FAC 61G15-33.004 |
| | NFPA-101 7.8, 7.9 |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS |
| | WHICH COORDINATE ALL LIGHTING ON PLANS AND FIXTURE |
| | LEGEND. PLEASE SEE THAT NO UPDATED CALCULATIONS WERE |
| | SUBMITTED BASED ON THE REVISED LIGHTING FIXTURES FROM |
| | PHASE ONE AND WILL BE REQUIRED BEFORE PHASE TWO |
| | CONSTRUCTION. |
| | THE INPUT DATA REPORT NEEDS ALL ITEMS ON PLANS WHICH |
| | CONSUME ENERGY AND PROVIDES EFFICIENCY TO BE ON THE |
| | IDR. |
| | PLEASE SEE 2001 FBC AND CHAPTER 13, 400.2, 400.3.A, |
| | 415.1.AB.1, 415.1.A, TABLE 4-15, 415.2 ETC. |
| | PLEASE KNOW THE REVISED CALCULATIONS WILL BE REQUIRED |
| | TO BE DONE UNDER THE CODE IN AFFECT AND UNDER PERMIT |
| | APPLICATION. |
| | |
| | |
| | 5) NOTE: PLEASE CLEARLY SEPARATE ELECTRICAL ON RISER |
| | FOR WHICH IS PART OF EACH PHASE AS THE PHASE I WORK IS |
| | COMPLETED. |
| | PLEASE SHOW HOW ALL NEW WORK WILL TAKE PLACE FOR |
| | INSTALLATION OF FEEDERS ETC TO EXISTING EQUIPMENT WHICH |
| | IS CURRENTLY ENERGIZED. THIS WAS GONE OVER SEVERAL |
| | YEARS AGO WHEN THIS PROJECT STARTED THAT THIS |
| | INFORMATION WOULD BE NEEDED AT A LATER DATE FOR PHASE |
| | II. |
| | FBC 104.1.2 |
| | ** PLEASE SEE THAT REVISIONS ARE BEING SUBMITTED FOR |
| | SHEETS AND ITEMS WHICH HAVE ALREADY HAD A FINAL |
| | INSPECTION. PLEASE DO NOT SUBMIT ANY REVISIONS FOR WORK |
| | WHICH WAS ALREADY COMPLETED EXCEPT THAT WORK WHICH IS |
| | DIRECTLY AFFECTED BY PHASE II. |
| | FOR EXAMPLE: WHY ARE ALL VOLTAGES ON PANELS BEING NOTED |
| | AS REVISIONS? |
| | PLEASE KNOW THAT A DETAILED RESPONSE LETTER/REVISION |
| | LISTING LETTER WOULD HELP ON THE REVIEW PROCESS. (NOT |
| | REQUIRED HOWEVER REVISIONS AS SUBMITTED ARE CONFUSING |
| | AND SOME CHANGES MADE ARE NOT UNDERSTOOD) |
| | PLEASE PROVIDE MORE INFORMATION. |
| | |
| | 6) NOTE: PLEASE SEE FBC CHAPTER 11 FOR ALL MINIMUM |
| | LEVELS FOR HORN/STROBE DEVICES. ALL LOCATIONS AND |
| | MINIMUM LEVELS SHALL BE SHOWN AND STATED. 11-4.28.1,.2 |
| | AND .3(4). |
| | ** EVEN AS THE FA SYSTEM IS UNDER A SEPARATE PERMIT |
| | THESE ITEMS ARE STILL REQUIRED ON PLANS FOR MINIMUM ADA |
| | COMPLIANCE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |