Plan Review Notes
Plan Review Notes For Permit 04111073
Permit Number 04111073
Review Stop E
Sequence Number 36
Notes
Date Text
2007-02-03 17:32:01REDLINED REVSION #7 ON RISER SHEET WHICH READS REV#6.
 REDLINED, E FIXURES ON E1.02, NOTE #4 MENTIONS
 CONTRACTOR MAY HAVE OPTION,THIS IS NOT THE OPTION OF
 THE CONTRACTOR. EM BATTERY BACK UP FIXTUURES WERE
 REDLINED ON PLANS PREVIOUSLY.THEMAIN ELECTRICAL
 ROOM, GEN RM, FIIRE PUMP AND ELEVATOR EQUIPMENT ROOMS
 SHOULD CONTAIN BATTERY BACK UP FIXTURES OF SOME SORT.