| Plan Review Notes For Permit 04111073 |
| Permit Number |
04111073 |
|
| Review Stop |
E |
| Sequence Number |
36 |
|
| Notes |
| Date |
Text |
| 2007-02-03 17:32:01 | REDLINED REVSION #7 ON RISER SHEET WHICH READS REV#6. | | | REDLINED, E FIXURES ON E1.02, NOTE #4 MENTIONS | | | CONTRACTOR MAY HAVE OPTION,THIS IS NOT THE OPTION OF | | | THE CONTRACTOR. EM BATTERY BACK UP FIXTUURES WERE | | | REDLINED ON PLANS PREVIOUSLY.THEMAIN ELECTRICAL | | | ROOM, GEN RM, FIIRE PUMP AND ELEVATOR EQUIPMENT ROOMS | | | SHOULD CONTAIN BATTERY BACK UP FIXTURES OF SOME SORT. |
|