| 2006-11-30 17:31:44 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE IN REVIEW OF LETTER PROVIDED WITH |
| | RESPECT TO ?INTEGRATED EQUIPMENT RATED SYSTEM AND |
| | "SERIES RATED" SYSTEM. PLEASE EXPLAIN HOW THIS WILL OR |
| | WILL NOT AFFECT THE SELECTIVE COORDINATION OF THE |
| | SYSTEM. |
| | PLEASE SEE 90.1A, 110.9, 110.10, 240.4A, 240.12 AND |
| | NFPA-110 (2002) 6.5. |
| | ALL SYSTEM SHALL BE RATED FOR THE AVAILABLE FAULT |
| | CURRENTS ON THE PRIMARY/FPL SIDE AND THE AVAILABLE |
| | FAULT CURRENT ON THE SECONDARY, HOWEVER PLEASE VERIFY |
| | AND SHOW HOW THIS CHANGING OF THE SYSTEM WILL AFFECT |
| | SECTIONS AS NOTED ABOVE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2006-11-21 12:25:39 | SPOKE TO ENGINEER, LTRT ON HOLD TO REVIEW FURTHER. |