| 2006-05-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04111073 |
| | ADD: 300 PEMBROKE PLACE |
| | CONT: THE WEITZ CO. |
| | TEL: (561)723-2443 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION REVIEW: |
| | ACTION: DENIED |
| | ROOF SHEATHING ASSEMBLIES |
| | 1) THERE ARE 2 SEPERATE PACKAGES (3)SETS |
| | IN EACH DATED APRIL 26/2006 AND MARCH |
| | 10/2006. |
| | |
| | 2) MARCH 10TH PACKAGE, DOESN'T PROVIDE |
| | CALCULATIONS FOR THE FASTENING OF THE |
| | DENSEDECK AND INSULATION TO THE METAL |
| | DECK. |
| | |
| | 3) THE RATIONAL ANALYSIS PROVIDED BY |
| | SLIDER ENGINEERING IS A COPY NOT AN |
| | ORIGINAL, NOT A ORIGINAL SIGNATURE |
| | ,RAISED SEAL OR DATE. |
| | FL ADMINISTRATIVE CODE, 61G15-23.002(1) |
| | |
| | 4) MIKE GINSBURG P.E. SIGNED& SEALED A |
| | COVER PAGE NOT INDEXING WHAT WAS |
| | INCLUSIVE OF THE DOCUMENT, INDEX PAGE IS |
| | THE NEXT SHEET. THERE ARE 5 SECTIONS |
| | NONE INDICATE HOW MANY PAGES ARE IN EACH |
| | SECTION. |
| | |
| | 5) INDEX PAGE INDICATES CALCULATION, |
| | WHERE, ONLY RATIONAL ANYLSIS PROVIDED. |
| | |
| | 6) HANSON HAS DETAIL SHEETS NOT SIGNED |
| | OR SEALED. |
| | |
| | |
| | APRIL 26/06 PACKAGE |
| | 7)COVER LETTER ALSO INDICATES |
| | CALCULATIONS TO BE IN THE PACKAGE BUT |
| | NONE WERE FOUND. |
| | |
| | 8) THE OLYMPIC ROOF FASTENER SUBMITTED |
| | INDICATES A 137.5 STATIC WITHDRAWL |
| | RESISTANCE WHEN ENBEDDED INTO 1/2" |
| | PLYWOOD. ALL THE PLYWOOD WAS TO BE |
| | REMOVED FROM THE DRAWINGS AND DENSEGLASS |
| | WAS TO BE USED TO BRING THE BUILDING |
| | BACK INTO COMPLIANCE.THE NEWEST |
| | ARCHITECTURAL SHEET( DELTA 4)A4.02 |
| | DETAILS 3& 4 STILL INDICATE 1/2" |
| | EXTERIOR FR SHEATHING TO BE USED, PLEASE |
| | CORRECT. |
| | THE VALUE FOR PENETRATING THE 22 GAUGE |
| | STEEL DECK IS 151.5. |
| | |
| | 9) THE GAF RUBEROID MODIFIED BITUMEN |
| | ROOFING REPORT SUBMITTED HAS THE SBS |
| | SYSTEM HIGHLIGHTED ,WHICH ONLY HAS A |
| | MAXIMUM DESIGN OF -60. LIMITATION #7 |
| | DOES ALLOW FOR ENHANCE FASTENING WITH |
| | THE RAS 117 STANDARD. THE STANDARD WAS |
| | SUBMITTED BUT THE DESIGN PROFESSIONAL |
| | HASN'T PROVIDED THE CALCULATIONS FOR |
| | FASTENING IN THE VARIOUS ZONES. THE |
| | FASTENER EXTRAPOLATION SHEET FOR THE |
| | BASE SHEET WAS SUBMITTED BUT NOT THE |
| | CALCS. |