| 2005-03-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | CITY WPB CODE |
| | |
| | A) FROM PREVIOUS REVIEW: THE COMMENT |
| | NUMBER SHALL REMAIN THE SAME TO AVOID |
| | CONFUSION. |
| | 1) SHT C3.01 DRAIN FOR SICSSOR LIFT TO |
| | STORM, MORE INFORMATION IS REQUIRED FOR |
| | THIS DRAIN, RESPONSE NOTED, BUT PLEASE |
| | INDICATE WHAT WILL BE DRAINING INTO THE |
| | STORM LINE. IS THIS FOR STORM WATER |
| | ONLY? - INDICATE IF THERE IS A |
| | POSSIBILITY OF OIL OR GREASE |
| | DRAINING/DRIPPING FROM THE LIFT AND |
| | ENTERING THE STORM WATER. |
| | 4) SHT A5.01 STAFF LOUNGE AND SERVING |
| | ROOM SINKS SHALL COMPLY WITH SECTION |
| | 11-4.24 AND ALL SUBSECTIONS. SUBMIT |
| | INFORMATION ON DETAIL. RESPONSE NOTED |
| | BUT THE FOLLOWING INFORMATION IS NOT |
| | SHOWN. SINK DEPTH 11-4.24.4, CLEAR FLOOR |
| | SPACE 11-4.24.5, EXPOSED PIPES AND |
| | SURFACES 11-4.24.6, & FAUCETS 11-4.24.7. |
| | 5) SHT A8.02DETAILS 1, 2, & 3 SHOW |
| | CLEAR FLOOR SPACE FOR ALL ACCESSIBLE |
| | FIXURES, TURNING AREA FOR ALL TOILET |
| | ROOMS. DOORS SHALL NOT OPEN INTO THE |
| | CLEAR FLOOR SPACE FOR ANY REQUIRED |
| | FIXTURE. RESPONSE NOTED, BUT THE |
| | FOLLOWING INFORMATION IS NOT SHOWN: |
| | DETAIL #2 SHOW CLEAR FLOOR SPACE FOR |
| | TOILET ROOMS 07 & 08 WITH TURNING AREA, |
| | SECTIONS 11-4.16.2, 11-4.19.3, & |
| | 11-4.22.3. EXPOSED PIPES AND SURFACES |
| | 11-4.19.6. ALSO IT APPEARS THAT THE |
| | DOORS ARE OPENING TINTO THE CLEAR FLOOR |
| | SPACE FOR THE LAVS. DISPENSER TO BE A |
| | MINIMUM OF 19" OFF THE FLOOR ON DETAIL |
| | 11/A802. FIGURE 29(B) |
| | 6) SHT A8.03 COFFEE CAFE ROOMS 1A03 & |
| | 1A04 REQUIRED THAT THE PLANS BE ROUTED |
| | TO THE PALM BEACH COUNTY HEALTH UNIT |
| | DIISION OF ENVIRONMENTAL HEALTH FOR |
| | REVIEW AND STAMPING PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. |
| | RESPONSE NOTED, BUT THE PLANS SHALL BE |
| | REVIEWED AND STAMPED PRIOR TO |
| | RESUBMITTING FOR REVIEW CITY WPB. |
| | SECTION 101.4.7. |
| | 7) SHT P102 SUBMIT CALCULATION FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106, & 1107 & ALL SUBSECTIONS. |
| | RESPONSE NOTED, BUT THE FOLLOWING |
| | INFORMATION IS REQUIRED. SHT P1.02 4" |
| | RWL'S AT COL. LINES 11/R, 10-11/N,& |
| | 10/J, MAXIMUM 1600 SF ON 4" HORIZONTAL. |
| | 6" REQUIRED OR SLOPE TO BE INDICATED AT |
| | 1/4"/FT. - SHT P1.03 RWL LINE AND OFD |
| | LINE ARE MISLABELED. - SHT P1.04 4" |
| | HORIZONTAL OFFSET, MAXIMUM 1600 SF, |
| | INDICATE SLOPE OR INCREASE TO 6". - SHT |
| | P1.06 MAXIMUM 1600 SF. INCREASE TO 6" OR |
| | INDICATE SLOPE. - SHT P1.07 RWL LINE |
| | FROM ROOF DRAIN AT COL. LINE 4/D SHALL |
| | BE RUN AT 1/4"/FT. SECTION 704.1 - SHT |
| | P1.08 4" OFD MISLABELED AS RWL NOT SIZED |
| | CORRECTLY. - PIPE SIZES MISSING ON SOME |
| | OFD'S AND RWL'S - SOME OFD PIPING IS |
| | UNDERSIZED - RWL PIPING IS MISLABELED AS |
| | OFD. - SOME SQUARE FOOTAGE IS NOT ADDED |
| | CORRECTLY. - 2" OFD PIPING NOT ADDED |
| | CORRECTLY. - P1.09 ALL OFD'S ARE |
| | MISLABELED AS RWL. |
| | 9) SHT P3.02 WATER RISER DIAGRAM, FULL |
| | OPEN VALVES ARE REQUIRED ON ALL WATER |
| | DOWN-FEED LINES PER SECTION 606.1(4). |
| | RESPONSE NOTED, BUT VALVES ARE STILL NOT |
| | SHOWN ON LINES TO FIXTURE L-2 ON ALL |
| | FLOORS. |
| | 12) SHT P3.03 DOMESTIC WATER RISER |
| | DIAGRAM, WATER HAMMER ARRESTORS SHALL BE |
| | LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. RESPONSE |
| | NOTED, BUT WHA'S ARE STILL SHOWN IN THE |
| | CEILING. PLEASE LOCAATE WHERE REQUIRED |
| | PER 604.9 (WASH MACHINE, ICE MAKER, DISH |
| | WASHER IF PROVIDED), |
| | 14) SHT P3.04 WATER FILTERS SHALL BE |
| | NSF-42 LISTED. SUBMIT MANUFACTURE |
| | SPECIFICATION SHEETS. SECTION 611. |
| | RESPONSE NOTED, BUT SHEETS WERE NOT |
| | SUBMITTED AS REQUESTED. |
| | 16) SHT P3.04 WASH SINK WATER PIPING, |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201. |
| | FULL OPEN VALVES REQUIRED ON ALL WATER |
| | DOWN-FEED LINES. SECTION 606.1(4). |
| | RESPONSE NOTED, BUT THE WHA'S ARE STILL |
| | IN THE CEILING AND THE WATER DOWN-FEED |
| | LINES DO NOT HAVE VALVES ON THEM. |
| | 18) SUBMIT A STORM BUILDING DRAIN |
| | ISOMETRIC SHOWING ALL PIPE SIZES, RISER |
| | CONNECTION, AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. ALSO SHOW |
| | SLOPE OF PIPE. SECTION 104.3.1.1. - |
| | SYSTEM CUT FIRST LINE OF COMMENTS FROM |
| | THE TEXT. STORM ISOMETRIC REQUIRED. |
| | 19) SUBMIT A CONDENSATED DRAIN SYSTEM |
| | ISOMETRIC. SHOW ALL PIPE SIZES, RISERS |
| | AND SHOW TERMINATION POINT FOR |
| | CONDENSATE. SECTION 104.3.1.1. RESPONSE |
| | NOTED, BUT CONDENSATE SHALL NOT DRAIN |
| | INTO THE SANITARY SYSTEM PER CITY CODE |
| | SECTION 90-125(2)(B). CONDENSATE SHALL |
| | DRAIN SEPARATELY OUT OF THE BUILDING AND |
| | CONNECT TO A CATCH BASIN, A STORM LINE, |
| | OR A DRYWELL. A RELIEF VENT IS REQUIRED |
| | AS THE CONDENSATE EXITS THE BUILDING. |
| | *************NEW COMMENT************ |
| | 1B) SHT P1.07 ENTIRE RUN FOR RWL FROM |
| | RD-2 TO 6" RWL DOWN TO LEVEL 2 TO RUN AT |
| | 1/4"/FT SLOPE. SECTION 704.1 |
| | 2B) NOTE: ONE SET OF PLUMBING SHEETS HAS |
| | RED LINES SHOWING LOCATION OF COMMENTS. |
| | PLEASE RESUBMIT THESE SHEETS FOR |
| | COMPARISON. |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |