| 2005-03-11 00:00:00 | 1. THE EXISTING ROTUNDA BUILDING IS |
| | NOT EQUIPPED WITH A SMOKE MANAGEMENT |
| | SYSTEM AND CONTAINS AN ATRIUM. A MEETING |
| | WAS HELD RECENTLY TO DISCUSS THE CODE |
| | ISSUES AND A CONSTRUCTION BOARD OF |
| | ADJUSTMENT AND APPEALS CASE IS |
| | SCHEDULED FOR MARCH 17, 2005. |
| | |
| | 2. THE PLANTING PLAN, PAGE L1.01 |
| | MAKES REFERENCE TO A TWENTY FOOT |
| | WIDE FIRE CORRIDOR TO THE WEST OF |
| | THE PROPOSED LIBRARY. WHAT LIVE LOADS |
| | OF FIRE APPARATUS IS IT EXPECTED TO |
| | SUPPORT. |
| | |
| | 3. PLEASE EXPLAIN PIVOT GATE DETAIL |
| | ON PAGE A1.03. WHAT PURPOSE DO THEY |
| | SERVE AND DO THEY CREATE ANY PROBLEMS. |
| | |
| | 4. THE TWO STUDIES SUBMITTED TO THE |
| | CITY MAKE REFERENCE TO THE GRAND |
| | STAIR. IS THERE ANY POSSIBILITY THAT |
| | THE GRAND STAIR WOULD BE USED FOR |
| | EXITING OR SHOULD ALL INTERESTED |
| | PARTIES AGREE THAT IT WILL NOT BE |
| | USED FOR ANY EXITING. |
| | |
| | 5. PLEASE INDICATE THAT PROPOSED |
| | CARD READERS WHEN INSTALLED WILL |
| | NOT INTERFERE WITH ANY EXIT ACCESS, |
| | OR EXITING. |
| | |
| | 6. THE REFLECTED CEILING PLAN |
| | LEVEL THREE, AREA A, EAST SIDE |
| | APPEARS TO NEED ANOTHER EXIT SIGN. |
| | EXIT SIGN PLACEMENT SHALL NOT |
| | EXCEED 100 FEET. |
| | |
| | 7. THE REQUIRED SMOKE EXHAUST SYSTEM |
| | SHALL BE CONNECTED TO THE GENERATOR |
| | SYSTEM. ALSO THE SMOKE EXHAUST SYSTEM |
| | FOR THE ATRIUM MUST BE PRE-TESTED AND |
| | WHEN TESTED WITH CITY OFFICIALS THE |
| | SYSTEM IS TO BE TESTED ON NORMAL AND |
| | ALSO ON EMERGENCY POWER. |
| | |
| | 8. EXIT DOORS ARE ALSO TO BE FISH |
| | SCALED WHEN THE SMOKE EXHAUST SYSTEM |
| | IS ACTIVATED TO ENSURE THAT ALL EXIT |
| | DOORS CAN BE OPENED EASILY. |
| | |
| | 9. PLEASE EXPLAIN FACTORY MOUNTED |
| | DISCONNECT SWITCH IN EXIT ACCESS AREA |
| | OF ROTUNDA STAIR AREA. PAGES E2.01 AND |
| | E2.03. |
| | |
| | 10. EMERGENCY GENERATOR ROOM SHALL |
| | BE AT LEAST TWO HOUR FIRE RATED DUE TO |
| | FUEL STORAGE BELOW THE GENERATOR. |
| | |
| | 11. SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |