| 2005-03-02 00:00:00 | ***** UNSAT ***** |
| | |
| | 1)NOTE: PLEASE SEE BLDG/FIRE AND |
| | MECHANICAL REVIEW NOTES FOR "ATRIUM". |
| | IT IS MY UNDER STANDING A VARIANCE IS TO |
| | BE APPLIED FOR WHICH MAY OR MAY NOT |
| | AFFECT ELECTRICAL PLANS. |
| | |
| | 2)NOTE: PLEASE SEE A DETAILED LETTER(?) |
| | WILL BE REQUIRED FOR PHASE II AND SHUT |
| | DOWN OF ELECTRICALEQUIPMENT BEFORE |
| | PULLING IN CONDUCTORS ETC. |
| | |
| | 3)NOTE: PLEASE SEE RESPONSE LTR |
| | MENTIONS; "THE LIGHTNING PROTECTION |
| | SYSTEM UNDER THE ELECTRICAL CONTRACTOR'S |
| | PERMIT (OR) A SEPARATE SUBCONTRACTOR |
| | PERMIT". PLEASE SEE SINCE LIGHTNING |
| | PROTECTION SYSTEM HAS BEEN REMOVED FROM |
| | PLANS. THIS WILL BE REQUIRED TO BE UNDER |
| | SEPARATE PERMIT AND MAY NOT BE UNDER |
| | ELECTRICAL CONTRACTORS BASEBUILDING |
| | ELECTRICAL PERMIT. |
| | |
| | 4)NOTE: PLEASE SEE RESPONSE LTR TO NOTE |
| | #4 FROM PREVIOUS REVIEW WHICH MENTIONS; |
| | A)L2B3: "THIS PANEL IS A SPARE PANEL FOR |
| | FUTURE LOADS". |
| | PLEASE CLARIFY, PANEL SCHEDULE FOR L2B3 |
| | CONTAINS NUMEROUS CIRCUITS AND LOADS?? |
| | |
| | 5)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS |
| | |
| | REVIEW; RESPONSE LTR PART; |
| | H) L1A2: RISER TO BE CHANGED TO 125A, |
| | FEEDER SIZE WILL BE CHANGED |
| | ACCORDINGLY". |
| | PLEASE SEE PANEL ON RISER NOW MENTIONS |
| | 150A MLO, AND PANEL INDICATES 150A MCB. |
| | PLEASE SEE INCREASE FROM LTR NOTING 125A |
| | WHICH IS FINE, HOWEVER RISER INDICATES |
| | MLO, WHEN MCB IS REQUIRED FOR SECONDARY |
| | SIDE OF TRANSFORMER. |
| | THIS SEEMS TO BE A MISPRINT? |
| | |
| | 6)NOTE: PLEASE SEE EH2 IS A 200MCB FED |
| | FROM MSB WITH A 200A BRKR. THIS IS OK, |
| | HOWEVER FEED FROM GENERATOR INDICATES A |
| | 400A BRKR FEEDING 400A ATS AND THEN TO |
| | 200A RATED PANEL/BRKR. |
| | PLEASE VERIFY THIS. |
| | PLEASE ALSO VERIFY CONDUCTORS/CONDUITS |
| | FROM GENERATOR TO NEW DISC'S, DISC'S |
| | BACK TO ATS AND ATS TO PANELS EH2. |
| | PLEASE VERIFY IF A TAP RULE IS OF SOME |
| | SORT IS BEING APPLIED. |
| | PLEASE ALSO SEE POSSIBLE VOLTAGE DROP. |
| | |
| | 7)NOTE: PLEASE SEE MANUFACTURE CUT/SPECS |
| | SHEETS STILL REQUIRED FOR FIRE PUMP/ |
| | FIRE PUMP CONTROLLER, ATS, GNERATOR AND |
| | SUB BASE FUEL FOR LIQUID TYPE FUELS. |
| | SPECS BOOKS DO NOT SEEM TO SPECIFICALLY |
| | DESIGNATE EQUIPMENT, SIZES ETC. |
| | |
| | |
| | 8)NOTE: PLEASE SEE SPEC BOOK PAGE |
| | 16075-8, MENTIONS BROWN, ORANGE, YELLOW |
| | FOR 277/480V SYSTEMS. |
| | PLEASE SEE "B" IS NOT A HIGH-LEG FOR |
| | 277/480V. PLEASE SEE LOCAL AMENDMENTS |
| | FOR BR/ PURPLE/ YELLOW.215 |
| | |
| | 9)NOTE: PLEASE SEE ONLY SET OF SPECS |
| | BOOKS WERE SUBMITTED, PLEASE SUBMIT TWO |
| | MORE SETS FOR REVIEW. |
| | |
| | PLEASE SEE DUE TO HAND WRITTEN NOTES |
| | ADDED FOR LOCKED ROTOR FOR FIRE PUMP ETC |
| | ANDCOMMENTS FOR CONDUCTORS/ CONDUITS |
| | AND PANEL L1A2, PLEASE REVISE AND |
| | REPRINT NEW RISER DIAGRAM SHEET. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |