| 2008-07-02 14:48:56 | REVISION DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P1.03 REVISION #3 INDICATED IN THE REVISION |
| | INDEX ON THE TITLE BLOCK IS NOT SHOWN ON THE FLOOR PLAN |
| | NOR ON THE RISER DIAGRAMS. ALSO NOT ALL |
| | CHANGES/REVISIONS ARE CLOUDED & NUMBERED WITH A |
| | REVISION NUMBER. SECTION 106.1.3. |
| | |
| | 2. SHT P3.05 REVISION #2 INDICATED IN THE REVISION |
| | INDEX ON THE TITLE BLOCK IS NOT SHOWN ON THE FLOOR PLAN |
| | NOR ON THE RISER DIAGRAMS. ALSO NOT ALL |
| | CHANGES/REVISIONS ARE CLOUDED & NUMBERED WITH A |
| | REVISION NUMBER. SECTION 106.1.3. |
| | |
| | 3. SHT P3.05 HORIZONTAL DRY VENTS ARE NOT APPROVED. |
| | SECTION 905.3. THIS IS SHOWN ON THE FLOOR PLAN AND THE |
| | RISER DIAGRAM FOR THE BASEMENT WORK. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |