| 2004-12-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) SHT C3.01 DRAIN FOR SCISSOR LIFT TO |
| | STORM. MORE INFORMATION IS REQUIRED FOR |
| | THIS DRAIN. WHAT IS IT DRAINING? SECTION |
| | 104.2.1. |
| | 2) SEPARATE PLANS AND PERMIT ARE |
| | REQUIRED FOR THE IRRIGATION. SECTION |
| | 104.1.1. |
| | 3) SHT A5.01 INTERIOR ELEVATION DETAILS |
| | NUMBERS 14/A5.01 & 17/A5.01 DO NOT |
| | REFLECT THE DETAIL NUMBERS SHOWN ON SHTS |
| | A1.05 (ROOM 12) & A1.06 (ROOM 03). |
| | PLEASE CORRELATE PLANS/DETAILS. SECTION |
| | 104.2.1. |
| | 4) SHT A5.01 STAFF LOUNGE & SERVING ROOM |
| | SINKS SHALL COMPLY WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. SUBMIT INFORMATION |
| | ON DETAIL. |
| | 5) SHT A8.02 DETAILS 1, 2, & 3 SHOW |
| | CLEAR FLOOR SPACE FOR ALL ACCESSIBLE |
| | FIXTURES, (DRINKING FOUNTAIN, URINAL |
| | ECT.), TURNING AREA FOR ALL TOILET |
| | ROOMS. DOORS SHALL NOT OPEN INTO THE |
| | CLEAR FLOOR SPACE FOR ANY REQUIRED |
| | FIXTURE. SECTIONS 11-4.15, 4-16, 4-18, |
| | 4-19, 4-22. (DETAIL 2/8.05 ROOM 7) - TWO |
| | DETAILS HAVE THE NUMBER "3" AND NO |
| | DETAIL "4". PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | 6) SHT A8.03 COFFEE CAFE ROOMS 1A03 & |
| | 1A04 REQUIRED THAT THE PLANS BE ROUTED |
| | TO THE PALM BEACH COUNTY HEALTH UNIT |
| | DIISION OF ENVIRONMENTAL HEALTH FOR |
| | REVIEW AND STAMPING PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. |
| | 7) SHT P1.02 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS PER |
| | SECTIONS 1106, & 1107 AND ALL |
| | SUBSECTIONS. SHOW SF OF EACH AREA WITH |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AS WELL AS ANY SF OF AREA OF |
| | ROOF THAT DRAIN ONTO THE ROOF AREAS FROM |
| | ABOVE IN THE CALCULATIONS. |
| | 8) SHT P3.01 SANT. RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| | MEET CODE REQUIREMENTS. THE WATER |
| | CLOSETS FOR THE MENS TOILET ROOMS ON |
| | EACH FLOOR ARE NOT SHOWN ON THE RISER. |
| | THE HORIZONTAL DRY VENTS AT THE BASE OF |
| | THE STACKS ARE NOT APPROVED PER SECTION |
| | 905.3. |
| | 9) SHT P3.02 WATER RISER DIAGRAM, FULL |
| | OPEN VALVES ARE REQUIRED ON ALL WATER |
| | DOWN FEED LINES PER SECTION 606.1(4). |
| | 10) GREASE INTECEPTOR NOT APPROVED |
| | INSIDE OF THE BUILDING AND SHALL BE |
| | LOCATED OUTSIDE. GREASE INTERCEPTOR |
| | SHALL BE SIZED BY RODNEY COMPO, |
| | ENVIRONMENTAL COMPLIANCE PER WASTE ORD. |
| | NUMBER 2938-96. CONTACT R. COMPO AT |
| | (561) 835-4074. APPROVAL SHEET SHALL BE |
| | ATTACHED TO PLANS WHEN RESUBMITTING. |
| | 11) SHT P3.03 FLOOR SINKS ARE REQUIRED |
| | FOR INDIRECT WASTE AND SHALL NOT BE A |
| | TRIPPING HAZARD. SECTION 802.3. - FLOOR |
| | DRAINS FOR DRAINING FLOORS ONLY. |
| | 12) SHT P3.03 DOMESTIC WATER RISER |
| | DIAGRAM, WATERHAMMER ARRESTORS SHALL |
| | BE LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| | SHOWN. PDI-WH 201 AND MANUF INSTALLATION |
| | INSTRUCTIONS. |
| | 13) SUBMIT A GREASE WASTE ISOMETRIC |
| | RISER DIAGRAM AND A SANT. RISER DIAGRAM |
| | FOR THIS FLOOR PLAN SHOWING WHERE IT |
| | CONNECTS TO THE BLDG DRAIN ISO. OR BLDG |
| | SEWER. SECTION 104.3.1.1. |
| | 14) SHT P3.04 WATER FILTERS SHALL BE |
| | NSF-42 LISTED. SUBMIT MANUF. |
| | SPECIFICATION SHEETS. SECTION 611. |
| | 15) SHT P3.04 ICE MAKER WATER SUPPLY |
| | REQUIRES BACKFLOW PROTECTION. SECTION |
| | 608.3. |
| | 16) SHT P3.04 WASH SINK WATER PIPING, |
| | WATER HAMMERS SHALL BE LOCATED NEAR THE |
| | FIXTURE NOT IN THE CEILING. PDI-WH 201. |
| | FULL OPEN VALVES REQUIRED PER SECTION |
| | 606.1(4). |
| | 17) SHT P3.05 SERVING ROOM WASTE RISER, |
| | ICE MACHINES TO INDIRECT WASTED. SECTION |
| | 802.3 & 802.3.2. |
| | 18) SUBMIT A STORM BUILDING DRAIN |
| | ISOMETRIC SHOWING ALL PIPE SIZES, RISER |
| | CONNECTION, AND SQUARE FOOTAGE AS IT |
| | ACCUMULATES IN THE SYSTEM. ALSO SHOW |
| | SLOPE OF PIPE. SECTION 104.3.1.1. |
| | 19) SUBMIT A CONDENSATED DRAIN SYSTEM |
| | ISOMETRIC. SHOW ALL PIPE SIZES, RISERS |
| | AND SHOW TERMINATION POINT FOR |
| | CONDENSATE. SECTION 104.3.1.1. |
| | |
| | |