| 2004-12-30 00:00:00 | DENIED: |
| | 1.PLAN SHEET A1.07, INDICATES A FUME |
| | HOOD LOCATED IN ROOM 02.THIS IS NOT |
| | INDICATED ON THE MECHANICAL PLAN. |
| | PLEASE CLARIFY WHAT THE FUME HOOD WILL |
| | BE UTILIZED FOR. |
| | |
| | 2.PLAN SHEET M1.01, PLAN INDICATE |
| | DUCT |
| | PENETRATING RATED WALL AT BS-3S & 3N, |
| | AND ALSO AT THE 2HR TEMPORARY WALL. |
| | PER |
| | 2001 FBC(M)607.6, SPECIFIC LOCATIONS OF |
| | THE FIRE DAMPERS ARE REQUIRED. |
| | EXCEPTIONS FOR FIRE DAMPERS SHALL |
| | COMPLY |
| | WITH 2001 FBC(M)607.1.3 #3 ITEMS 1 |
| | THROUGH 4.PLEASE ANNOTATE ON THE PLAN |
| | SHOULD THE EXCEPTION APPLY. |
| | |
| | 3.PLAN SHEET M1.02, PLAN INDICATES |
| | DUCTS AND OR GRILLES PENETRATING OR |
| | TERMINATING AT RATED WALLS/PARTITIONS - |
| | ROOM # 19,20,21,35, 1S-2 & 1S-1.2001 |
| | FBC(M) 607.6. |
| | |
| | 4.PLAN SHEET M1.03, DUCT/GRILLE |
| | PENETRATIONS OR TERMINATION AT RATED |
| | WALLS/PARTITIONS - ROOM 11, 15, 1S-3S & |
| | 3N. |
| | |
| | 5.PLAN SHEET M1.03, CLARIFY CHASE IN |
| | ROOM 04, IS THIS RATED? |
| | |
| | 6.PLAN SHEET M1.03, CLARIFY FRESH AIR |
| | INTAKE & BRANCH DUCT AT EXTERIOR WALL |
| | IS |
| | THIS A RELIEF GRILLE OR SUPPLY? |
| | |
| | 7.PLAN SHEET M1.03, PLEASE IDENTIFY |
| | AHU IN THE MECHANICAL ROOM #15.PLEASE |
| | IDENTIFY ALL EQUIPMENT. |
| | |
| | 8.PER 2001 FBC 414.5, ATRIUM SHALL BE |
| | SEPARATED FROM ADJACENT SPACES WITH A 1 |
| | HOUR FIRE SEPARATION.THIS IS NOT |
| | INDICATED ON PLAN SHEETS A0.02 & A0.03. |
| | |
| | 9.PLAN SHEET M7.02 INDICATES SMOKE |
| | EXHAUST AND CALCULATIONS FOR PHASE I. |
| | PLEASE CLAIRFY THE FOLLOWING: |
| | 1) WILL THERE BE NO COMUNICATION |
| | BETWEEN |
| | THE TWO PHASES UNTIL COMPLETTION OF |
| | PHASE II. |
| | 2) UPON COMPLETION OF PHASE II WILL |
| | THEY |
| | REMAIN "SEPARATED" BY WALLS & DOORS OR |
| | IS THE INTENT TO HAVE THE TWO |
| | STRUCTURES |
| | BE "OPEN" TO EACH OTHER. |
| | 3) SHOULD THE INTENT BE FOR "OPEN" THE |
| | TWO STRUCTURES INTO ONE, THIS WILL THEN |
| | CHANGE THE CALCULATION FOR THE "ATRUIM" |
| | SMOKE EXHAUST. |
| | |
| | 10.PLEASE PROVIDE ADDITIONAL |
| | INFORMATION ON PHASE II.IT APPEARS BY |
| | DEFININTION THAT IT ALSO HAS AN ATRIUM. |
| | |
| | 11.PHASE II INDICATES "BASEMENT" |
| | SHOULD THIS SPACE ACTUALLY BE BELOW |
| | GRADE, SHOW COMPLIANCE WITH 2001 FBC(M) |
| | 403.6.7. |
| | |
| | 12.FAN SHUTDOWN BY DUCT SMOKE |
| | DETECTORS REQUIRED PER 2001 |
| | FBC(M)606.2.1. |
| | |
| | 13.NO COMBUSTIBLE ALLOWED IN THE |
| | RETURN AIR PLEUNUM, 2001 FBC(M)602.2.1. |
| | |
| | 14.PLANS INDICATE ROOF ACCESS.WILL |
| | ANY MECHANICAL EQUIPMENT BE LOCATED IN |
| | THIS AREA? |
| | |
| | 15.PROVIDE ADDITIONAL INFORMATION ON |
| | THE GENERATOR.INDICATE DISTANCES TO |
| | DOORS, WINDOWS, AND FRESH AIR INTAKES. |
| | PROVIDE ELEVATION FOR THE MUFFLER |
| | EXHAUST TERMINATION. |
| | |
| | 16.INDICATE WHAT TYPE OF "FUEL" OR |
| | GAS |
| | WILL BE USED FOR THE GENERATOR. |
| | |
| | PLEASE PROVIDE A RESPONSE LETTER |
| | ADDRESSING COMMENTS TO HELP EXPEDITE |
| | FUTURE REVIEW. |
| | |