| 2004-12-22 00:00:00 | *************** UNSAT ***************** |
| | |
| | PALM BEACH ATLANTIC UNIVERSITY |
| | WARREN LIBRARY |
| | |
| | 1)NOTE: PLEASE SEE 230.72 FOR GROUPING |
| | OF MAINS. |
| | PLEASE SEE LOCATION OF EHDP1. THIS WILL |
| | BE REQUIRED TO BE LOCATED IN CLOSE |
| | PROXIMITY OF MSB. |
| | 230.72B THE ONE OR MORE ADDITIONAL |
| | SERVICE DISCONNECTING MEANS FOR FIRE |
| | PUMPS, FOR LEGALLY REQUIRED STANDBY, OR |
| | FOR OPTIONAL STANDBY SERVICES PERMITTED |
| | BY 230.2 SHALL BE INSTALLED REMOTE FROM |
| | THE ONE TO SIX SERVICE DISCONNECTING |
| | MEANS FOR NORMAL SERVICE TO MINIMIZE |
| | THE |
| | POSSIBILITY OF SIMULTANEOUS |
| | INTERRUPTION |
| | OF SUPPLY. HOWEVER, A RESPONSE FROM |
| | NFPA |
| | MENTIONS REMOTE MAY BE A CLOSE AS 10'. |
| | THIS WAS BROUGHT UP IN PREVIOUS |
| | MEETINGS |
| | AND DECIDED THIS LOCATION WAS TO BE |
| | MOVED? |
| | |
| | 2)NOTE: PLEASE SEE LIGHTNING PROTECTION |
| | SYSTEM:IF THIS WILL BE INSTALLED |
| | UNDER |
| | MAIN ELECTRICAL CONTRACTORS PERMIT: |
| | PLEASE SUBMIT COMPLETE PLANS FOR THIS |
| | UNDER NFPA-780. IF THIS WILL BE |
| | INSTALLED BY ASUB-CONTRACTOR THIS MAY |
| | BE DONE UNDER SEPARATE PERMIT. PLEASE |
| | ONLY REFERENCE ON PLANS AND REMOVE |
| | LIGHNING AS SHOWN. |
| | |
| | 3)NOTE: PLEASE SEE CONDUIT FILL FOR |
| | 1-1/2" CONDUIT SIZE TO HDP2 ON MSB. |
| | |
| | 4)NOTE: PLEASE CORRELATE PANEL |
| | SCHEDULES, PANELS AND EQUIPMENT SHOWN |
| | ON |
| | RISER DIAGRAM. |
| | PLEASE SEE THE FOLLOWING AS A SOME |
| | NOTED |
| | ON PLAN REVIEW. |
| | |
| | L2B3-NO PANEL SCHEDULE? |
| | EL3- NO PANEL SCHEDULE? |
| | L1B3- PANEL NOT INDICATED ON LEGEND ON |
| | E5.04, MISSING INFORMATION ON RISER, |
| | OCP,SIZE? |
| | H2B1- 225A ON RISER 400A ON PANEL |
| | SCHEDULE. |
| | EH2- NOT ON RISER? |
| | H1B2- 400A ON PANEL SCHEDULE, 225A ON |
| | RISER. |
| | L4A1- 250A ON RISER 225A ON PANEL |
| | SCHEDULE. |
| | L1A2- 125A ON PANEL SCHEDULE,225A ON |
| | RISER. |
| | L2B1- 250A ON RISER AND 400A ON PANEL |
| | SCHEDULE. |
| | |
| | 5)NOTE: PLEASE SEE SIZE OF OCP FOR |
| | TRANSFORMER T1A1, MAX 125% 450.3 |
| | |
| | 6)NOTE: PLEASE SEE A MCB WILL BE |
| | REQUIRED FOR L3A2 ON THE LOAD SIDE OF |
| | THE TRANSFORMER. PLEASE SEE LOADS ARE |
| | NOT SPECIFIC.IN ADDITION TO THE |
| | REQUIREMENTS OF 408.13, A POWER |
| | PANELBOARD WITH SUPPLY CONDUCTORS THAT |
| | INCLUDE A NEUTRAL AND HAVING MORE THAN |
| | 10 PERCENT OF ITS OVERCURRENT DEVICES |
| | PROTECTING BRANCH CIRCUITS RATED 30 |
| | AMPERES OR LESS SHALL BE PROTECTED BY |
| | AN |
| | OVERCURRENT PROTECTIVE DEVICE HAVING A |
| | RATING NOT GREATER THAN THAT OF THE |
| | PANELBOARD. THE OVERCURRENT PROTECTIVE |
| | DEVICE SHALL BE LOCATED WITHIN OR AT |
| | ANY |
| | POINT ON THE SUPPLY SIDE OF THE |
| | PANELBOARD. |
| | |
| | 7)NOTE: PLEASE SUBMIT COMPLETED |
| | INFORMATION FOR FIRE PUMP. |
| | PLEASE SEE 695.4B1 THE OVERCURRENT |
| | PROTECTIVE DEVICE(S) SHALL BE SELECTED |
| | OR SET TO CARRY INDEFINITELY THE SUM OF |
| | THE LOCKED-ROTOR CURRENT OF THE FIRE |
| | PUMP MOTOR(S) AND THE PRESSURE |
| | MAINTENANCE PUMP MOTOR(S) AND THE |
| | FULL-LOAD CURRENT OF THE ASSOCIATED |
| | FIRE |
| | PUMP ACCESSORY EQUIPMENT WHEN CONNECTED |
| | TO THIS POWER SUPPLY. |
| | PLEASE SEE SECONDARY OCP IS NOT |
| | PERMITTED AS SHOWN.695.5BTHE PRIMARY |
| | OVERCURRENT PROTECTIVE DEVICE(S) SHALL |
| | BE SELECTED OR SET TO CARRY |
| | INDEFINITELY |
| | THE SUM OF THE LOCKED-ROTOR CURRENT OF |
| | THE FIRE PUMP MOTOR(S) AND THE PRESSURE |
| | MAINTENANCE PUMP MOTOR(S) AND THE |
| | FULL-LOAD CURRENT OF THE ASSOCIATED |
| | FIRE |
| | PUMP ACCESSORY EQUIPMENT WHEN CONNECTED |
| | TO THIS POWER SUPPLY. SECONDARY |
| | OVERCURRENT PROTECTION SHALL NOT BE |
| | PERMITTED. |
| | |
| | 8)NOTE: PLEASE SEE NO INFORMATION WAS |
| | GIVEN FOR FIRE PUMP CONTROLLER. PLEASE |
| | SEE RISER DOES NOT INDICATE ANY METHOD |
| | OF TRANSFER OF POWER FROM FPL AND |
| | GENERATOR FOR FIRE PUMP? |
| | PLEASE COMPLETE AND SUBMIT ALL |
| | MANUFACTURE SPECS FOR FIRE PUMP, FIRE |
| | PUMP CONTROLLER, ATS, GENERATOR, FUEL |
| | ETC. |
| | |
| | 9)NOTE: PLEASE SEE SOME ELECTRICAL ROOM |
| | LAYOUTS DO NOT MEET 110.26 FOR CODE |
| | COMPLIANCE. |
| | PLEASE SEE PLANS AND ADJUST. |
| | |
| | 10)NOTE: PLEASE SHOW GROUNDING |
| | ELECTRODE |
| | SYSTEM PER 250.50. COULD NOT LOCATE ANY |
| | ON ELECTRICAL PLANS SUBMITTED. |
| | |
| | 11)NOTE: PLEASE SHOW GROUNDING FOR ALL |
| | TRANSFORMERS OR A COMMON DETAIL FOR |
| | TRANSFORMERS PER 250.30 |
| | |
| | 12)NOTE: PLEASE SEE NOTES FROM ALL |
| | OTHER |
| | REVIEWERS ON THE SCOPE OF WORK FOR |
| | PAHSE |
| | ONE AND TWO AND POSSIBLE SEPARATE |
| | PERMITS FOR EACH OR ALL WORK MUST BE |
| | COMPLETED UNDER ONE PHASE. |
| | PHASE ONE WILL NOTBE PERMITTED TO |
| | HAVE |
| | POWER WITH FEEDERS ETC FOR PHASE TWO |
| | NOT |
| | INSTALLED AND PULLED/SAFED OFF ETC. |
| | PLEASE SEE THAT A MEETING TO DICUSS THE |
| | PROCESS OF PHASES, COMPLETIONS, C/O'S |
| | ETC. |
| | |
| | 13)NOTE: PLEASE SEE DUE TO COMPLETE |
| | INFORMATION NOT SUBMITTED AT THIS TIME |
| | A |
| | COMPLETE REVIEW FOR CODE COMPLIANCE CAN |
| | NOT BE DONE. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | |
| | |
| | |
| | IF SYSTEM IS |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |