Plan Review Notes
Plan Review Notes For Permit 04111067
Permit Number 04111067
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-03 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING
 POOLS
  
  
 1) ?424.2.21.2 SKIMMERS. APPROVED
 SURFACE SKIMMERS ARE REQUIRED AND
 SHALL BE INSTALLED IN STRICT
 ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
 SKIMMERS SHALL BE INSTALLED ON THE
 BASIS
 OF ONE PER 1000 SQ FT OF SURFACE
 AREA OR FRACTION THEREOF, AND SHALL
 BE DESIGNED FOR A FLOW RATE OF AT
 LEAST 25 GPM PER SKIMMER.
  
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
  
  