| Plan Review Notes For Permit 04111067 |
| Permit Number |
04111067 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-03 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING | | | POOLS | | | | | | | | | 1) ?424.2.21.2 SKIMMERS. APPROVED | | | SURFACE SKIMMERS ARE REQUIRED AND | | | SHALL BE INSTALLED IN STRICT | | | ACCORDANCE WITH THE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS. | | | SKIMMERS SHALL BE INSTALLED ON THE | | | BASIS | | | OF ONE PER 1000 SQ FT OF SURFACE | | | AREA OR FRACTION THEREOF, AND SHALL | | | BE DESIGNED FOR A FLOW RATE OF AT | | | LEAST 25 GPM PER SKIMMER. | | | | | | 2) FBC-2001 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | | SHEETS REQUIRED. (SUBMITTAL) | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|