Plan Review Notes
Plan Review Notes For Permit 04111029
Permit Number 04111029
Review Stop E
Sequence Number 1
Notes
Date Text
2004-11-24 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SEE ALL SHEETS ARE
 REQUIRED TO AHVE A TITLE BLOCK WHEN
 SIGNED AND SEALED BY THE ENGINEER.
 FAC 61G15-23.002, FS 471
  
 2)NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION FOR DESIGNER.
 FS 481.223
 PLEASE SEE USES OF PROTECTED WORDS.
  
 3)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 BATH REQUIRED TO BE AT 20A, #12.
  
 4)NOTE: PLEASE SEE FBC CHAPTER 34 WHICH
 REQUIRES GFI'S AND SD'S TO BE RBOUGHT UP
 TO CODE IN EXISTING DWELLING FOR
 ADDITIONS OF 25% OR MORE.
 3401.7.1.2.1
  
 PLEASE SEE NOTES #1&2 ARE FOR ALL TRADES
 AND ALL SHEETS WHEATHER OR NOT COMMENT
 IS MADE BY THAT REVIEWER.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  