Plan Review Notes
Plan Review Notes For Permit 04110993
Permit Number 04110993
Review Stop E
Sequence Number 6
Notes
Date Text
2006-01-31 00:00:00******* UNSAT *****
  
 1)NOTE: PLEASE CORRELATE RISER AND
 FEEDERS FOR TENANT MAINS 1 AND 10.
 PLEASE SEE THESE ARE SHOWN AS 150A'S,
 YET FEEDER NOTE #9 INDICATES 32'S. AWG.
 PLEASE SEE 310.16,240.4
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 UNIT #10 INDICATES THIS PANEL AS 100A'S?
 SHEET E-1.12
  
 3)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 LAYOUT ON 1.10A WHICH SHOWS TWO MAINS
 WITH CONDUIT JOINING BOTH MAINS. PLEASE
 VERIFY THIS AS EACH SEEM TO FEED
 DIFFERENT GUTTERS ETC?
 215.5
  
 PLEASE KNOW, DEPENDING ON FIRE REVIEW,
 SHEETS FOR UNITS MAY BE STAMPED AND
 PASSED FOR REVIEW, HOWEVER SHEETS
 MENTIONED ABOVE SHALL BE REMOVED.
 CORRECTED REVISIONS WILL BE REQUIRED TO
 BE SUBMITTED SEPARTELY.
 IF FIRE REVIEW PROCEEDS INTO A "P"
 STATUS, UNIT LAYOUTS WILL BE STAMPED FOR
 ROUGH INSPECTIONS. *** PLEASE KEEP IN
 MIND, PLANS SUBMITTED ARE STILL SHOWING
 SHEETS WHICH INDICATE "OPTIONS", PLEASE
 KNOW, ALL "OPTIONS" MUST BE REVISED TO
 THE INDIVIDUAL UNITS BEFORE ROUGH.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF NEW SHEETS ADDRESSING
 COMMENTS AS NOTED ABOVE ARE SUBMITTED
 AND INSERTED INTO SETS BEFORE FIRE
 REVIEW IS COMPLETED, THEN PLEASE CALL TO
 SET UP A MEETING TO DO SO.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]