| 2006-01-31 00:00:00 | ******* UNSAT ***** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER AND |
| | FEEDERS FOR TENANT MAINS 1 AND 10. |
| | PLEASE SEE THESE ARE SHOWN AS 150A'S, |
| | YET FEEDER NOTE #9 INDICATES 32'S. AWG. |
| | PLEASE SEE 310.16,240.4 |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| | UNIT #10 INDICATES THIS PANEL AS 100A'S? |
| | SHEET E-1.12 |
| | |
| | 3)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM |
| | LAYOUT ON 1.10A WHICH SHOWS TWO MAINS |
| | WITH CONDUIT JOINING BOTH MAINS. PLEASE |
| | VERIFY THIS AS EACH SEEM TO FEED |
| | DIFFERENT GUTTERS ETC? |
| | 215.5 |
| | |
| | PLEASE KNOW, DEPENDING ON FIRE REVIEW, |
| | SHEETS FOR UNITS MAY BE STAMPED AND |
| | PASSED FOR REVIEW, HOWEVER SHEETS |
| | MENTIONED ABOVE SHALL BE REMOVED. |
| | CORRECTED REVISIONS WILL BE REQUIRED TO |
| | BE SUBMITTED SEPARTELY. |
| | IF FIRE REVIEW PROCEEDS INTO A "P" |
| | STATUS, UNIT LAYOUTS WILL BE STAMPED FOR |
| | ROUGH INSPECTIONS. *** PLEASE KEEP IN |
| | MIND, PLANS SUBMITTED ARE STILL SHOWING |
| | SHEETS WHICH INDICATE "OPTIONS", PLEASE |
| | KNOW, ALL "OPTIONS" MUST BE REVISED TO |
| | THE INDIVIDUAL UNITS BEFORE ROUGH. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF NEW SHEETS ADDRESSING |
| | COMMENTS AS NOTED ABOVE ARE SUBMITTED |
| | AND INSERTED INTO SETS BEFORE FIRE |
| | REVIEW IS COMPLETED, THEN PLEASE CALL TO |
| | SET UP A MEETING TO DO SO. |
| | |