| Date |
Text |
| 2006-01-12 00:00:00 | ********** UNSAT ************ |
| | |
| | |
| | 1)NOTE: RISER DIAGRAM AHS NOW BEEN |
| | COMPLETELY REVISED. PLEASE SEE MAINS |
| | HAVE NOW BEEN INCREASED AND VOLTAGES |
| | HAVE BEEN CHANGED FROM 480V TO 208V. |
| | PLEASE SEE NO REVISED PANELS, PANEL |
| | SCHEDULES, OR LOAD CALCUALTIONS WERE |
| | SUBMITTED FOR THIS. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE 250.66 FOR MIN SIZING |
| | FOR GROUNDING ELECTRODE CONDUCTOR. |
| | PLEASE SEE A 2/0 MIN APPEARS TO BE |
| | REQUIRED. PLEASE SEE THIS IS REQUIRED |
| | FOR ALL MAINS. (4). |
| | |
| | 3)NOTE: PLEASE SEE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR" IS NOW BEING SHOWN |
| | FROM METER TO MAIN. |
| | PLEASE SEE 250.6, THIS EQP GRND SHOULD |
| | ONLY BE INSTALLED AFTER THE FIRST MEANS |
| | OF DISCONNECT. |
| | |
| | 4)NOTE: PLEASE INDICATE THE |
| | SIZE/AMPERAGES OF METERS. PLEASE SEE |
| | METER FOR SPACE 7/8 NOW APPEAR TO BE |
| | FEEDING TWO MAINS. PLEASE ALSO SEE |
| | CONDUCTORS FOR DISCONNECT #2 SEEMS TO BE |
| | FEEDING THROUGH THE OTHER MAIN. PLEASE |
| | SEE MAIN DISCONNECT IS BEING USED AS A |
| | RACEWAY FOR 2ND MAIN. |
| | PLEASE VERIFY AS METER SHOULD BE DOUBLE |
| | LUGGED FOR THIS INSTALLATION. |
| | |
| | |
| | 5)NOTE: PLEASE SEE HOUSE PANEL AND MAIN |
| | SEEMS TO BE STRICKEN FROM PLANS WITH A |
| | HIGHLIGHTER FOR SOME REASON? |
| | PLEASE VERIFY. |
| | 215.5 |
| | |
| | ** PLEASE KNOW ALL OPTIONS FOR UNITS AND |
| | REVISIONS SHOULD BE SUBMITTED FOR REVIEW |
| | AND ON JOB-SITE BEFORE ANY ROUGH |
| | ELECTRICAL INSPECTION IS CALLED IN. |
| | PLEASE SEE ORIGINAL PLANS WERE STAMPED |
| | FOR THIS. |
| | THIS IS ONLY A NOTE, AS IT HAS TO THE |
| | ATTENTION OF THIS OFFICE THAT ROUGHS ARE |
| | BEING CALLED IN FOR INSPECTIONS WITHOUT |
| | HAVING THE LATEST UPDATED STMAPED PLANS |
| | ON JOBSITE FOR INSPECTION. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW ALONG WITH OTHER MISSING |
| | INFORMATION FOR REVIEW. IF THERE ARE ANY |
| | QUESTIONS, PLEASE CALL. |
| | |