Plan Review Notes
Plan Review Notes For Permit 04110993
Permit Number 04110993
Review Stop M
Sequence Number 4
Notes
Date Text
2005-08-29 00:00:00PROVISO:2ND REQUEST
 1.WAREHOUSE UNITS (EXAMPLE 006) THAT
 HAVE THE DESIGN CAPACITY OR WITH
 AGGREGATE AIR GREATER THAN 2,000 CFM
 SHALL HAVE FAN SHUTDOWN BY DUCT SMOKE
 DETECTORS IN ACCORDANCE WITH 2001 FBC(M)
 606.2.1 & 606.2.2.
  
 2.PER 2001 FBC(M)306.5, EQUIPMENT
 LOCATED AT A HEIGHT GREATER THE 16 FT
 ABOVE FLOOR LEVEL SHALL HAVE PERMANENT
 MEANS OF ACCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.