| Plan Review Notes For Permit 04110993 |
| Permit Number |
04110993 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2005-08-29 00:00:00 | PROVISO:2ND REQUEST | | | 1.WAREHOUSE UNITS (EXAMPLE 006) THAT | | | HAVE THE DESIGN CAPACITY OR WITH | | | AGGREGATE AIR GREATER THAN 2,000 CFM | | | SHALL HAVE FAN SHUTDOWN BY DUCT SMOKE | | | DETECTORS IN ACCORDANCE WITH 2001 FBC(M) | | | 606.2.1 & 606.2.2. | | | | | | 2.PER 2001 FBC(M)306.5, EQUIPMENT | | | LOCATED AT A HEIGHT GREATER THE 16 FT | | | ABOVE FLOOR LEVEL SHALL HAVE PERMANENT | | | MEANS OF ACCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|