| 2005-11-14 00:00:00 | ************ UNSAT ************ | | | | | | 1)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM | | | IS NOW BEING SHOWN AT A DETACHED BLDG. | | | PLEASE SEE 225.31 -225.39 FOR FEEDERS | | | COMING INTO MAIN BLDG. A DISCONNECTING | | | MEANS FOR EACH IS REQUIRED AND ALL MAINS | | | ARE REQUIRED TO BE GROUPED ETC. 252.31, | | | 225.34. | | | | | | 2)NOTE: PLEASE SEE MIN CLEARENCES PER | | | 110.26 ARE NOT MET IN THIS NEW | | | ELECTRICAL ROOM SHOWN. | | | PLEASE SEE SCALE AS SHOWN MENTIONS | | | 1/2"PER FT. | | | | | | 3)NOTE: PLEASE PROVIDE GROUNDING | | | ELECTRODE SYSTEM AT DETACHED MAIN BLDG. | | | PER 250.32 | | | | | | 4)NOTE: PLEASE PROVIDE A REVISED RISER | | | DIAGRAM WITH CHANGES AS SHOWN AND | | | CHANGES TO BE MADE BY THE ABOVE | | | COMMENTS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASEDO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-11-10 00:00:00 | *********NOTES*** | | | | | | | | | PLANS TO BE FAILED AND COMMENTS TO | | | FOLLOW. | | | DO NOT CONSTRUCT DETACHED ELECTRICAL | | | ROOM, AS SHOWN THIS WILL NOT PERMITTED. | | | | | | | | | ** CALLED OWNER'S REP, FOR ELECTRICAL | | | COMMENTS TO FOLLOW. |
|