2005-11-14 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 IS NOW BEING SHOWN AT A DETACHED BLDG.
 PLEASE SEE 225.31 -225.39 FOR FEEDERS
 COMING INTO MAIN BLDG. A DISCONNECTING
 MEANS FOR EACH IS REQUIRED AND ALL MAINS
 ARE REQUIRED TO BE GROUPED ETC. 252.31,
 225.34.
  
 2)NOTE: PLEASE SEE MIN CLEARENCES PER
 110.26 ARE NOT MET IN THIS NEW
 ELECTRICAL ROOM SHOWN.
 PLEASE SEE SCALE AS SHOWN MENTIONS
 1/2"PER FT.
  
 3)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE SYSTEM AT DETACHED MAIN BLDG.
 PER 250.32
  
 4)NOTE: PLEASE PROVIDE A REVISED RISER
 DIAGRAM WITH CHANGES AS SHOWN AND
 CHANGES TO BE MADE BY THE ABOVE
 COMMENTS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASEDO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-11-10 00:00:00*********NOTES***
  
  
 PLANS TO BE FAILED AND COMMENTS TO
 FOLLOW.
 DO NOT CONSTRUCT DETACHED ELECTRICAL
 ROOM, AS SHOWN THIS WILL NOT PERMITTED.
  
  
 ** CALLED OWNER'S REP, FOR ELECTRICAL
 COMMENTS TO FOLLOW.