3 |
|
| Notes |
| Date |
Text |
| 2005-06-06 00:00:00 | PROVISO: | | | 1.UNIT #001 & 006 ARE REQUIRED TO HAVE | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS IN | | | ACCORDANCE WITH 2001 FBC,M 606.2.1 & | | | 606.2.2, A/C SYSTEMS THAT HAVE THE | | | DESIGN CAPACITY OR WITH AGGREGATE AIR | | | GREATER THAN 2,000 CFM SHALL HAVE FAN | | | SHUTDOWN. | | | | | | 2.PLEASE CLARIFY ACCESS TO THE AHU'S | | | LOCATED IN THE WAREHOUSE AREA AT 19 FT | | | TO THE TOP OF THE AHU. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|