Plan Review Notes
Plan Review Notes For Permit 04110993
Permit Number 04110993
Review Stop M
Sequence Number 3
Notes
Date Text
2005-06-06 00:00:00PROVISO:
 1.UNIT #001 & 006 ARE REQUIRED TO HAVE
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS IN
 ACCORDANCE WITH 2001 FBC,M 606.2.1 &
 606.2.2, A/C SYSTEMS THAT HAVE THE
 DESIGN CAPACITY OR WITH AGGREGATE AIR
 GREATER THAN 2,000 CFM SHALL HAVE FAN
 SHUTDOWN.
  
 2.PLEASE CLARIFY ACCESS TO THE AHU'S
 LOCATED IN THE WAREHOUSE AREA AT 19 FT
 TO THE TOP OF THE AHU.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.