Plan Review Notes
Plan Review Notes For Permit 04110993
Permit Number 04110993
Review Stop P
Sequence Number 2
Notes
Date Text
2005-03-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A) FROM PREVIOUS REVIEW:
 1) SHT L-3 SHOW THE LOCATION OF THE
 CONTROLLER/TIMER, AND RAIN SENSOR.
 SECTION 104.2.1.
 5) INDICATE THE SF AREA FOR EACH UNIT TO
 CALCULATED THE MINIMUM FACILITIES PER
 TABLES 1003.1 & 403.1. RESPONSE NOTED,
 BUT NO SF LOCATED.
 6) SHT A3.03 SINK IN BREAKROOM SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. SHOW THE FOLLOWING:
 11.4.24.2 HEIGHT, 11-4.24.3 KNEE
 CLEARANCE, 11-4.24.4 SINK DEPTH,
 11-4.24.5 CLEAR FLOOR SPACE, FORWARD
 APPROACH REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK,
 11-4.24.6 EXPOSED PIPES AND SURFACES, &
 11-4.24.7 FAUCETS. - NO RESPONSE NOTED.
 9) SHT A3.09 DETAIL #8 PROVIDE
 CALCULATIONS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.26.3(2)(3)(4). NO
 CALCULATIONS FROM THE ENGINEER NOTED.
 10) SHT A3.09 SHOW COMPLIANCE WITH
 SECTION 11-4.19.4 EXPOSED PIPES &
 SURFACES. RESPONSE NOTED, BUT EXPOSED
 PIPES STILL REQUIRE SHALL BE INSULATED
 TO PREVENT INJURY.
 13) SHTS P5.01 & P5.02 WATER RISER
 DIAGRAMS, SECTION 606.1(4) FULL OPEN
 VALVES ARE REQUIRED ON EVERY WATER DOWN
 FEED PIPE. SECTION 606.2(2) SHUT OFF
 VALVES REQUIRED FOR HOSE BIBBS. RESPONSE
 NOTED, BUT NO ISOMETRICS WERE FOUND ON
 SHT P4.01. THESE VALVES SHALL BE SHOWN
 ON ALL ISOMETRIC WATER RISER DIAGRAM.
 **************NEW COMMENTS************
 1B) SHT P5.02 SANT. RISER DIAGRAM #2/401
 BRANCH CONNECTION TO THE SINK FITTING IN
 AGAINST THE FLOW. FITTINGS SHALL BE
 INSTALLED TO GUIDE SEWAGE AND WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3
 2B) SHT A3.01 UNIT SPACE DESIGNATED 002
 SHOWS NO FIXTURES. PLEASE CLAIRFY.
 SECTION 104.2.1.
 3B) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE FOR EACH BUILDING. SECTION
 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]