Plan Review Notes
Plan Review Notes For Permit 04110993
Permit Number 04110993
Review Stop M
Sequence Number 2
Notes
Date Text
2005-03-04 00:00:00DENIED:
 REFERENCE COMMENTS FROM THE PREVIOUS
 REVIEW:
 COMMENT #4 - AUXILIARY DRAIN PAN WITH
 OVERFLOW PROTECTION REQUIRED.AUXILIARY
 DRAIN PANS ARE REQUIRED UNDER COILS
 WHICH CONDENSATION WILL OCCUR WHERE
 DAMAGE TO THE BUILDING OR BUILDING
 CONTENTS CAN OCCUR (2001 FBC/M 307.2.3).
  
 COMMENT #5 - DUCT SMOKE DETECTORS
 REQUIRED IN UNITS THAT HAVE THE DESIGN
 CAPACITY GREATER THAN 2,000.PROVIDE
 LETTER FROM THE ENGINEER AT THE
 MANUFACTURER INDICATING THAT THE UNIT
 WILL NOT BE ABLE TO EXCEED 2,000 CFM.
 AC-3 IS A 5 TON UNIT AND MAY HAVE THE
 CAPACITY TO EXCEED 2,000 CFM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.