| 2005-03-04 00:00:00 | DENIED: | | | REFERENCE COMMENTS FROM THE PREVIOUS | | | REVIEW: | | | COMMENT #4 - AUXILIARY DRAIN PAN WITH | | | OVERFLOW PROTECTION REQUIRED.AUXILIARY | | | DRAIN PANS ARE REQUIRED UNDER COILS | | | WHICH CONDENSATION WILL OCCUR WHERE | | | DAMAGE TO THE BUILDING OR BUILDING | | | CONTENTS CAN OCCUR (2001 FBC/M 307.2.3). | | | | | | COMMENT #5 - DUCT SMOKE DETECTORS | | | REQUIRED IN UNITS THAT HAVE THE DESIGN | | | CAPACITY GREATER THAN 2,000.PROVIDE | | | LETTER FROM THE ENGINEER AT THE | | | MANUFACTURER INDICATING THAT THE UNIT | | | WILL NOT BE ABLE TO EXCEED 2,000 CFM. | | | AC-3 IS A 5 TON UNIT AND MAY HAVE THE | | | CAPACITY TO EXCEED 2,000 CFM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|