Plan Review Notes
Plan Review Notes For Permit 04110993
Permit Number 04110993
Review Stop P
Sequence Number 1
Notes
Date Text
2004-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT L-3 INDICATE WATER SOURCE FOR THE
 IRRIGATION, IF SOURCE IS CITY WATER, A
 BACKFLOW IS REQUIRED TO BE INSTALLED BY
 A LICENCED PLUMBING CONTRACTOR. SHOW THE
 LOCATION OF THE RPZ BACKFLOW, THE
 CONTROLLER/TIMER, AND THE RAIN SENSOR.
 SECTION 104.2.1.
 2) SHT L-3 SEE FAC 61G1-16.004 THE FIRM
 NAME, ADDRESS AND TELEPHONE NUMBER IS
 REQUIRED ON THE TITLE BLOCK. FS
 481.2055
 3) SHT A0.01 INDICATE TYPE AND AMOUNT OF
 MATERIAL TO BE STORED IN THE WAREHOUSE.
 MORE COMMENTS MAY FOLLOW DEPENDING ON
 THE RESPONSE. SECTION 104.2.1.
 4) SHT A3.01 W/C, LAV, SERVICE SINK, AND
 DRINKING FOUNTAIN ARE REQUIRED IN EACH
 SPACE. SEE UNIT 002. PLEASE CLAIRFY.
 SECTOPM 104.2.1. TABLE 403.1 SECTION
 410.1.
 5) INDICATE THE SQUARE FOOTAGE AREA FOR
 EACH UNIT TO CALCULATE THE MINIMUM
 FACILITIES PER TABLES 1003.1 & 403.1.
 6) SHT A3.03 SINK IN BREAKROOM SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. SHOW THE FOLLOWING:
 11-4.24.2 HEIGHT - 11-4.24.3 KNEE
 CLEARANCE - 11-4.24.4 SINK DEPTH -
 11-4.24.5 CLEAR FLOOR SPACE, FORWARD
 APPROACH REQUIRED AND SHALL EXTEND A
 MAXIMUM OF 19" UNDERNEATH THE SINK -
 11-4.24.6 EXPOSED PIPES AND SURFACES -
 11-4.24.7 FAUCETS.
 7) SHT A3.05 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 TOTAL SQUARE FOOTAGE AREA FOR THE ROOF
 AND SHOW 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO ROOF AREA.
 SHOW THE TOTAL AREA DRAINING TO EACH
 ROOF DRAIN. ROOF DRAINS IN EACH AREA
 WITH OUT SECONDARY ROOF DRAINS,
 (SCUPPERS), SHALL BE SIZED FOR PRIMARY
 AND SECONDARY SCUPPER DRAINS TOTAL
 AREA.
 SECTIONS 1106 AND 1107 AND ALL
 SUBSECTIONS. TABLES 1106.2 & 1106.3.
 8) INDICATE THE SIZE OF ALL DOWNSPOUTS.
 SEE TABLE 1106.2
 9) SHT A3.09 DETAIL #8 PROVIDE
 CALCULATIONS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.26.3(2)(3)& (4).
 10) SHT A3.09 FOR ACCESSIBLE W/C'S SHOW
 CLEAR FLOOR SPACE, SECTION 11-4.16.2 AND
 FOR LAVS SHOW EXPOSED PIPES AND SURFACES
 SECTION 11-4.19.4.
 11) SUBMIT A FINISH SCHEDULE SHOWING
 REQUIREMENTS FOR PUBLIC TOILET ROOMS PER
 SECTION 1204.2.
 12) SHT P4.01 DETAIL #1 MORE INFORMATION
 REQUIRED ON THE WATER JACKET PIT. WHAT
 IS A WATER JACKET PIT AND WHAT IS ITS
 USE? SUBMIT MANUF. SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR REVIEW.
 SECTION 104.2.1.
 13) SHTS P5.01 & P5.02 WATER RISER
 DIAGRAMS. SECTION 606.1(4) FULL OPEN
 VALVES ARE REQUIRED ON EVERY WATER DOWN
 FEED PIPE. AND SECTION 606.2(2) SHUT OFF
 VALVES REQUIRED FOR HOSE BIBBS.
 14) SHT P5.02 SANT. RISER #2/401 DOES
 NOT REFLECT THE FLOOR PLAN. LAV AND SINK
 ARE MISLABELED. SECTION 104.2.1.
 14) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]