| Plan Review Notes For Permit 04110993 |
| Permit Number |
04110993 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-12-17 00:00:00 | DENIED: | | | 1.PLAN SHEET M8.01 MECHANICAL | | | EQUIPMENT STAND DETAIL, PLEASE NOTE | | | TABLE THAT IS INDICATED & HEIGHT | | | DEMENSION IS INCORRECT.REFERENCE TABLE | | | 1511.7 OF THE 2001 FBC.TABLE INDICATES | | | HEIGHT OF THE LEGS THIS SHOULD READ | | | ABOVE THE ROOF SURFACE.THE WIDTH OF | | | EQUIPMENT LESS THAN 36" SHOULD NOT BE | | | MIN. BUT 24". | | | | | | 2.PLANS DO NOT INDICATE INSULATION ON | | | THE REFRIGERANT PIPING.SHOW COMPLIANCE | | | WITH 2001 FBC CHAPTER 13 SUB-CHAPTER | | | 611.1.ABC.1. | | | | | | 3.PLEASE NOTE EQUIPMENT LOCATED ON | | | ROOF THAT EXCEEDS 16 FT SHALL HAVE A | | | PERMENANT MEANS OF ACCESS PER 2001 | | | FBC(M)306.5. | | | | | | 4.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED.DETAIL ON PLAN | | | SHEET M8.01 DOES NOT INDICATE AN | | | AUXILIARY PAN. | | | | | | 5.PLEASE NOTE, EQUIPMENT WITH THE | | | DESIGN CAPACITY GREATER THAN 2,000 CFM | | | SHALL BE EQUIPPED WITH DUCT SMOKE | | | DETECTORS AND HAVE NOTIFICATION TO | | | ALARM/STROBE PER 2001 FBC(M)606.2.1 & | | | 606.4.1 #2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|