2004-12-17 00:00:00DENIED:
 1.PLAN SHEET M8.01 MECHANICAL
 EQUIPMENT STAND DETAIL, PLEASE NOTE
 TABLE THAT IS INDICATED & HEIGHT
 DEMENSION IS INCORRECT.REFERENCE TABLE
 1511.7 OF THE 2001 FBC.TABLE INDICATES
 HEIGHT OF THE LEGS THIS SHOULD READ
 ABOVE THE ROOF SURFACE.THE WIDTH OF
 EQUIPMENT LESS THAN 36" SHOULD NOT BE
 MIN. BUT 24".
  
 2.PLANS DO NOT INDICATE INSULATION ON
 THE REFRIGERANT PIPING.SHOW COMPLIANCE
 WITH 2001 FBC CHAPTER 13 SUB-CHAPTER
 611.1.ABC.1.
  
 3.PLEASE NOTE EQUIPMENT LOCATED ON
 ROOF THAT EXCEEDS 16 FT SHALL HAVE A
 PERMENANT MEANS OF ACCESS PER 2001
 FBC(M)306.5.
  
 4.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED.DETAIL ON PLAN
 SHEET M8.01 DOES NOT INDICATE AN
 AUXILIARY PAN.
  
 5.PLEASE NOTE, EQUIPMENT WITH THE
 DESIGN CAPACITY GREATER THAN 2,000 CFM
 SHALL BE EQUIPPED WITH DUCT SMOKE
 DETECTORS AND HAVE NOTIFICATION TO
 ALARM/STROBE PER 2001 FBC(M)606.2.1 &
 606.4.1 #2.
  