| 2004-12-20 00:00:00 | 1. WET FIRE HYDRANTS ARE REQUIRED |
| | PRIOR TO, DURING AND AFTER |
| | CONSTRUCTION. |
| | |
| | 2. SUITABLE ROADS ARE TO BE PROVIDED |
| | FOR FIRE AND PARAMEDICAL EQUIPMENT |
| | DURING CONSTRUCTION. |
| | |
| | 3. KNOX-BOXES WILL BE REQUIRED. |
| | |
| | 4. PROPER CLEARANCES ARE REQUIRED TO |
| | ALL PROPOSED FIRE HYDRANTS. |
| | |
| | 5. ELECTRONIC SWITCHES, CHAIN AND |
| | LOCKS REQUIRED ON FIRE LINE BACKFLOW |
| | DEVICE. |
| | |
| | 6. ALL PROPOSED MEZZANINES TO COMPLY |
| | WITH THE FLORIDA BUILDING CODE AND |
| | THE FLORIDA FIRE PREVENTION CODE WITH |
| | REGARDS TO MEZZANINES. |
| | |
| | 7. BUILDING ADDRESS REQUIRED ON PROPER |
| | ELEVATION. A MINIMUM OF AT LEAST 6" |
| | NUMBERS ARE REQUIRED. |
| | |
| | 8. PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATIONS FOR WALLS AND CEILINGS. |
| | |
| | 9. PLEASE PROVIDE PRESCRITPIVE STRENGTH |
| | REQUIREMENTS FOR ALL HANDRAILS AND |
| | GUARDRAILS. |
| | |
| | 10. PLEASE INDICATE WHAT ITEMS WILL |
| | BE STORED IN THE BUILDING. ARE ANY |
| | FLAMMABLE OR COMBUSTIBLE LIQUIDS, |
| | SOLIDS OR GASES PLANNED. |
| | |
| | 11. ANY STORAGE RACKS PLANNED. |
| | |
| | 12. THE FIRE ALARM SYSTEM SHALL |
| | BE MONITORED BY A UL LISTED FIRE |
| | ALARM COMPANY LISTED FOR CENTRAL |
| | STATION SERVICE. |
| | |
| | 13. KNOX-BOX LOCKING CAPS SHALL BE |
| | PROVIDED. |
| | |
| | 14. SEPARATE PLANS AND PERMITS |
| | REQUIRED FOR THE FIRE SPRINKLER SYSTEM. |
| | |
| | 15. PROVIDE SEPARATE PLANS AND PERMITS |
| | FOR FIRE ALARM SYSTEM. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |