Plan Review Notes
Plan Review Notes For Permit 04110993
Permit Number 04110993
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-12-20 00:00:001. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER
 CONSTRUCTION.
  
 2. SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT
 DURING CONSTRUCTION.
  
 3. KNOX-BOXES WILL BE REQUIRED.
  
 4. PROPER CLEARANCES ARE REQUIRED TO
 ALL PROPOSED FIRE HYDRANTS.
  
 5. ELECTRONIC SWITCHES, CHAIN AND
 LOCKS REQUIRED ON FIRE LINE BACKFLOW
 DEVICE.
  
 6. ALL PROPOSED MEZZANINES TO COMPLY
 WITH THE FLORIDA BUILDING CODE AND
 THE FLORIDA FIRE PREVENTION CODE WITH
 REGARDS TO MEZZANINES.
  
 7. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF AT LEAST 6"
 NUMBERS ARE REQUIRED.
  
 8. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 9. PLEASE PROVIDE PRESCRITPIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDRAILS.
  
 10. PLEASE INDICATE WHAT ITEMS WILL
 BE STORED IN THE BUILDING. ARE ANY
 FLAMMABLE OR COMBUSTIBLE LIQUIDS,
 SOLIDS OR GASES PLANNED.
  
 11. ANY STORAGE RACKS PLANNED.
  
 12. THE FIRE ALARM SYSTEM SHALL
 BE MONITORED BY A UL LISTED FIRE
 ALARM COMPANY LISTED FOR CENTRAL
 STATION SERVICE.
  
 13. KNOX-BOX LOCKING CAPS SHALL BE
 PROVIDED.
  
 14. SEPARATE PLANS AND PERMITS
 REQUIRED FOR THE FIRE SPRINKLER SYSTEM.
  
 15. PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE ALARM SYSTEM.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910