| 2004-12-02 00:00:00 | IN ELEC FOR REVIEW. |
| | ************** UNSAT ****************** |
| | |
| | WAREHOUSE PROJECT: |
| | 5405 N. HAVERHILL |
| | 04110993 |
| | |
| | REVIEWED FOR CODE COMPLIANCE UNDER 2002 |
| | NEC. |
| | |
| | 1)NOTE: PLEASE SEE UNIT #2, SHOWS TO BE |
| | FUTURE UNIT, YET MEZZ FLR AREA SHOWS |
| | LTS, BUT NOT TO ANY CIRCUITS? |
| | PLEASE CLARIFY. |
| | |
| | 2)NOTE: PLEASE SEE UNITS #'S 13,26 |
| | INDICATE SHOW ROOMS. PLEASE SEE 210.62 |
| | AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| | INSTALLED DIRECTLY ABOVE A SHOW WINDOW |
| | FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR |
| | FRACTION THEREOF OF SHOW WINDOW AREA |
| | MEASURED HORIZONTALLY AT ITS MAXIMUM |
| | WIDTH. |
| | SHOW WINDOWS USUALLY EXTEND FROM FLOOR |
| | TO CEILING FOR MAXIMUM DISPLAY. TO |
| | DISCOURAGE FLOOR RECEPTACLES AND |
| | UNSIGHTLY EXTENSION CORDS LIKELY TO |
| | CAUSE PHYSICAL INJURY, RECEPTACLES MUST |
| | BE INSTALLED DIRECTLY ABOVE A SHOW |
| | WINDOW, AND ONE RECEPTACLE IS REQUIRED |
| | FOR EVERY 12 LINEAR FT OR ?MAJOR |
| | FRACTION THEREOF? (6 FT OR MORE). SEE |
| | 220.3(B)(7) AND 220.12(A) FOR |
| | INFORMATION REGARDING LOAD COMPUTATIONS |
| | FOR SHOW WINDOWS. |
| | IT IS NOTEDON ONE OF THE PANEL |
| | SCHEDULES FOR L-26 "SHOWROOM RECEPTS, |
| | HOWEVER THESE APPEAR TO BE CLOSE TO FLR |
| | LEVEL? |
| | |
| | 3)NOTE: PLEASE INDICATE CIRCUITING FOR |
| | ALL A/C EQUIPMENT. PLEASE SEE THERE ARE |
| | SOME A/C COND UNITS SHOWN ON ROOF, YET |
| | THESE DO NOT SHOW ANY HOOK-UPS, CIRCUITS |
| | ETC.? |
| | PLEASE SEE 440.11 WHICH REQUIRES |
| | DISCONNECTING MEANS CAPABLE OF |
| | DISCONNECTING AIR-CONDITIONING AND |
| | REFRIGERATING EQUIPMENT, INCLUDING |
| | MOTOR-COMPRESSORS AND CONTROLLERS FROM |
| | THE CIRCUIT CONDUCTORS. |
| | |
| | 4)NOTE: PLEASE SEE ALL OPTS AS SHOWN ON |
| | E-1.08. IF ANY OF THESE OPTIONS ARE |
| | TAKENAND DIFFER FROM PLANS SHOWN, THEN |
| | PLANS WILL BE REQUIRED TO BE REVISED |
| | BEFORE ROUGH FOR WHICH OPTION IS TAKEN |
| | FOR WHICH UNIT. THIS IS ONLY A NOTE |
| | GIVEN AT THIS TIME. |
| | |
| | 5)NOTE: PLEASE SEE 250.50 FOR REQUIRED |
| | POINTS OF ATTACHMENT FOR GROUNDING |
| | ELECTRODE SYSTEM. |
| | IF AVAILABLE ON THE PREMISES AT EACH |
| | BUILDING OR STRUCTURE SERVED, EACH ITEM |
| | IN 250.52(A)(1) THROUGH (A)(6) SHALL BE |
| | BONDED TOGETHER TO FORM THE GROUNDING |
| | ELECTRODE SYSTEM. CONCRETE-ENCASED |
| | ELECTRODE,METAL UNDERGROUND WATER PIPE, |
| | ETC. |
| | |
| | 6)NOTE: PLEASE SEE THERE IS AN EQUIPMENT |
| | GROUNDING CONDUCTOR SHOWN FROM FPL |
| | TRANSFORMER TO MAIN # 2. |
| | PLEASE SEE 250.6,250.24 |
| | OBJECTIONABLE CURRENT OVER GROUNDING |
| | CONDUCTORS. |
| | A PREMISES WIRING SYSTEM SUPPLIED BY A |
| | GROUNDED AC SERVICE SHALL HAVE A |
| | GROUNDING ELECTRODE CONDUCTOR CONNECTED |
| | TO THE GROUNDED SERVICE CONDUCTOR, AT |
| | EACH SERVICE, IN ACCORDANCE WITH |
| | 250.24(A)(1) THROUGH (A)(5). |
| | THE CONNECTION SHALL BE MADE AT ANY |
| | ACCESSIBLE POINT FROM THE LOAD END OF |
| | THE SERVICE DROP OR SERVICE LATERAL TO |
| | AND INCLUDING THE TERMINAL OR BUS TO |
| | WHICH THE GROUNDED SERVICE CONDUCTOR IS |
| | CONNECTED AT THE SERVICE DISCONNECTING |
| | MEANS. |
| | |
| | 7)NOTE: PLEASE SEE NOTE #9 FOR RISER |
| | DIAGRAM ON E 1.10. |
| | PLEASE SEE 250.122 FOR SIZING OF THE |
| | EQUIPMENT GROUNDING CONDUCTOR. |
| | COPPER, ALUMINUM, OR COPPER-CLAD |
| | ALUMINUM EQUIPMENT GROUNDING CONDUCTORS |
| | OF THE WIRE TYPE SHALL NOT BE SMALLER |
| | THAN SHOWN IN TABLE 250.122 BUT SHALL |
| | NOT BE REQUIRED TO BE LARGER THAN THE |
| | CIRCUIT CONDUCTORS SUPPLYING THE |
| | EQUIPMENT. |
| | SOME SHOWN AS #10 ON 100A OCP ETC. |
| | PLEASE SEE NOTE #17. |
| | |
| | 8)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | EQUIPMENT SIZES. |
| | RISER SHOWS SOME 100A FEEDS TO 60A |
| | DISCONNECTING MEANS. PLEASE SEE |
| | EQUIPMENT MUST BE RATED FOR FEED. |
| | PLEASE SEE 1-6,14-19= 100A FEEDS TO 60A |
| | DISC'S. #20&21 150A FEEDS TO 100A |
| | DISC'S.???? |
| | |
| | 9)NOTE: PLEASE VERIFY SERVICE LOCATION |
| | ON PLANS. THIS COULD NOT BE LOCATED. |
| | PLEASE SEE 230.72 FOR GROUPING OF |
| | MAINS. |
| | PLEASE ALSO SEE 230.70 THE SERVICE |
| | DISCONNECTING MEANS SHALL BE INSTALLED |
| | AT A READILY ACCESSIBLE LOCATION EITHER |
| | OUTSIDE OF A BUILDING OR STRUCTURE OR |
| | INSIDE NEAREST THE POINT OF ENTRANCE OF |
| | THE SERVICE CONDUCTORS. |
| | THE TWO TO SIX DISCONNECTS AS PERMITTED |
| | IN 230.71 SHALL BE GROUPED. EACH |
| | DISCONNECT SHALL BE MARKED TO INDICATE |
| | THE LOAD SERVED. |
| | |
| | 10)NOTE: PLEASE SHOW LOCATION OF |
| | DISCONNECTS, TRANSFORMERS IN UNITS. |
| | THESE COULD NOT BE LOCATED ON PLANS. |
| | 215.5 |
| | |
| | 11)NOTE: PLEASE SEE 250.30 FOR GROUNDING |
| | OF TRANSFOMERS. |
| | GROUNDING SEPARATELY DERIVED |
| | ALTERNATING-CURRENT SYSTEMS. |
| | A SEPARATELY DERIVED AC SYSTEM THAT IS |
| | GROUNDED SHALL COMPLY WITH 250.30(A)(1) |
| | THROUGH (6). PLEASE SHOW THE ATTACHMENT |
| | ON RISER. |
| | |
| | 12)NOTE: PLEASE SHOW ALL CONTINUOUS |
| | LOADS AT 125%.FEEDERS SHALL BE PROTECTED |
| | AGAINST OVERCURRENT IN ACCORDANCE WITH |
| | THE PROVISIONS OF PART I OF ARTICLE 240. |
| | WHERE A FEEDER SUPPLIES CONTINUOUS LOADS |
| | OR ANY COMBINATION OF CONTINUOUS AND |
| | NONCONTINUOUS LOADS, THE RATING OF THE |
| | OVERCURRENT DEVICE SHALL NOT BE LESS |
| | THAN THE NONCONTINUOUS LOAD PLUS 125 |
| | PERCENT OF THE CONTINUOUS LOAD. |
| | THE AMPACITY OF THE SERVICE-ENTRANCE |
| | CONDUCTORS BEFORE THE APPLICATION OF ANY |
| | ADJUSTMENT OR CORRECTION FACTORS SHALL |
| | NOT BE LESS THAN EITHER (1) OR (2). |
| | LOADS SHALL BE DETERMINED IN ACCORDANCE |
| | WITH ARTICLE 220. AMPACITY SHALL BE |
| | DETERMINED FROM 310.15. THE MAXIMUM |
| | ALLOWABLE CURRENT OF BUSWAYS SHALL BE |
| | THAT VALUE FOR WHICH THE BUSWAY HAS BEEN |
| | LISTED OR LABELED. |
| | (1) THE SUM OF THE NONCONTINUOUS LOADS |
| | PLUS 125 PERCENT OF CONTINUOUS LOADS |
| | (2) THE SUM OF THE NONCONTINUOUS LOAD |
| | PLUS THE CONTINUOUS LOAD IF THE |
| | SERVICE-ENTRANCE CONDUCTORS TERMINATE IN |
| | AN OVERCURRENT DEVICE WHERE BOTH THE |
| | OVERCURRENT DEVICE AND ITS ASSEMBLY ARE |
| | LISTED FOR OPERATION AT 100 PERCENT OF |
| | THEIR RATING. |
| | THIS WILL BE FOR INDIVIUAL UNITS AND |
| | HOUSE PANELS. |
| | |
| | 13)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | PER EACH MAIN. |
| | PLEASE SHOW LOAD CALCULATIONS, PLEASE |
| | SHOW PER 220.3,220.10,220.11,220.13 |
| | ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE ALSO INDICATE LOAD FOR EACH |
| | PANEL, ON THAT PARTICULAR PANEL |
| | SCHEDULE. |
| | PLEASE SEE THERE IS A PANEL "X" WHICH IS |
| | NOTED FOR SOME TYPICAL UNITS, HOWEVER |
| | THERE ARE CIRCUITS AND LOADS INDICATED |
| | ON SOME OF THESE UNITS WHICH ARE NOT |
| | SHOWN ON THIS "TYPICAL" PANEL |
| | SCHEDULE.? |
| | PLEASE CORRELATE. ONE UNIT NOTED,#13 |
| | |
| | 14)NOTE: PLANS CONTAIN NOTES IN MANY |
| | LOCATION WITH REFERENCE TO EXISTING |
| | SERVICE AND EXISTING PHASE 1, YET THE |
| | TITLE BLOCK AND PLANS REFERENCE THIS AS |
| | BEING PHASE -1. ?? |
| | PLEASE SEE LOAD CALCS INDICATE |
| | "EXISTING" BUILDING CAPACITY??? |
| | PLEASE SEE E1.10,1.09 |
| | |
| | 15)NOTE: PLEASE SEE SPRINKLER MONITOR |
| | PANEL DETAIL. PLEASE SEE MISSING |
| | EQUIPMENT GROUNDING PER 250.110 |
| | EXPOSED NON?CURRENT-CARRYING METAL PARTS |
| | OF FIXED EQUIPMENT LIKELY TO BECOME |
| | ENERGIZED SHALL BE GROUNDED. |
| | |
| | 16)NOTE: PLEASE CLARIFY IF FIRE |
| | SPRINKLER PIPING IS METAL? PLEASE SEE |
| | 250.104 .THE METAL WATER PIPING SYSTEM |
| | SHALL BE BONDED AS REQUIRED IN (1), (2), |
| | (3), OR (4) OF THIS SECTION. THE BONDING |
| | JUMPER(S) SHALL BE INSTALLED IN |
| | ACCORDANCE WITH 250.64(A), (B), AND (E). |
| | THE POINTS OF ATTACHMENT OF THE BONDING |
| | JUMPER(S) SHALL BE ACCESSIBLE. |
| | |
| | 17)NOTE: PLEASE SEE 408.16.EACH LIGHTING |
| | AND APPLIANCE BRANCH-CIRCUIT PANELBOARD |
| | SHALL BE INDIVIDUALLY PROTECTED ON THE |
| | SUPPLY SIDE BY NOT MORE THAN TWO MAIN |
| | CIRCUIT BREAKERS OR TWO SETS OF FUSES |
| | HAVING A COMBINED RATING NOT GREATER |
| | THAN THAT OF THE PANELBOARD. |
| | PLEASE SEE MOST PANELS ARE SHOWN AS |
| | MLO. |
| | PLEASE ALSO SEE 240.21 |
| | |
| | 18)NOTE: PLEASE SEE MOST OF THE WATER |
| | HEATERS SHOWN INDICATE 40A OCP FOR 6KW |
| | UNITS WHICH IS FINE, YET THERE ARE A |
| | COUPLE WITH 50A OCP. PLEASE SEE MAX OCP |
| | FOR WATER HEATER IS 150%. PLEASE ADJUST |
| | OCP.A BRANCH CIRCUIT SUPPLYING A FIXED |
| | STORAGE-TYPE WATER HEATER THAT HAS A |
| | CAPACITY OF 450 L (120 GAL) OR LESS |
| | SHALL HAVE A RATING NOT LESS THAN 125 |
| | PERCENT OF THE NAMEPLATE RATING OF THE |
| | WATER HEATER. |
| | IF THE BRANCH CIRCUIT SUPPLIES A SINGLE |
| | NON?MOTOR-OPERATED APPLIANCE, THE RATING |
| | OF OVERCURRENT PROTECTION SHALL BE 150% |
| | MAX . 422.11 |
| | |
| | 19)NOTE: PLEASE SEE HOUSE PANEL "HP-1" |
| | DOES NOT INDICATE FEED FOR TRANSFORMER |
| | TO SPRINKLER MONT PANEL? |
| | PLEASE SHOW. 215.5 |
| | |
| | 20)NOTE: PLEASE SEE ALL LOADS FOR ALL |
| | AHU'S ON PANEL SCHEDULES. SOME SHOW |
| | ACTUAL LOADS, SOMEDO NOT INDICATE FULL |
| | KW LOAD FOR A/C UNITS?? |
| | PLEASE CORRELATE ALL. |
| | 215.5 |
| | |
| | 21)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PANELS, DISCONNECTS. ETC. |
| | PLEASE SEE UNIT #1 ON RISER INDICATES A |
| | 400A DISC , YET UNIT #1IS 100A'S?? |
| | SHOWS UNIT #2 AS 100A AND PLANS INDICATE |
| | #2 AS 400A. |
| | |
| | 22)NOTE: PLEASE SEE A/C LOAD/DISC ON |
| | PLANS, SHOWN FOR 50A LOAD? |
| | |
| | 23)NOTE: PLEASE SEE WIND LOADING FOR |
| | POLES ARE LISTED AS 120MPH. PLEASE SEE |
| | WE ARE UNDER THE FBC 140 MPH RATING. |
| | PLEASE SUBMIT WIND LOADS AND SPECS FOR |
| | SITE LIGHTING POLES FOR BLDG REVIEW. |
| | THIS IS REQUIRED AT THIS TIME. PLEASE |
| | ALSO ADJUST ELECTRICAL PLANS FOR 140 |
| | MPH. |
| | LIGHT POLES ARE ALSO NOTED AS MENTIONING |
| | TO MATCH "EXISTING" PHASE-1 ?? |
| | |
| | 24)NOTE: PLEASE SEE "L-26" ON E1.12 DOES |
| | NOT INDICATE BUS-RATING.? |
| | 215.5 |
| | |
| | 25)NOTE: PLEASE ALSO SEE CIRCUITING OF |
| | EM/EXT LTS. |
| | PLEASE SEE 700.12E FOR CIRCUITING |
| | REQUIREMENTS. |
| | INDIVIDUAL UNIT EQUIPMENT FOR EMERGENCY |
| | ILLUMINATION SHALL CONSIST THE BRANCH |
| | CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT |
| | SERVING THE NORMAL LIGHTING IN THE AREA |
| | AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. |
| | |
| | 26)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SEE BLDG REVIEW NOTES FOR |
| | REQUIREMENTS OF POSSIBLE "SPEACIAL |
| | INSPECTOR" AND NEEDING THREE (3) SETS OF |
| | PLANS. |
| | |
| | 27)NOTE: PLEASE SEE POSSIBLE NOTES FROM |
| | OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS.(FIRE,BLDG |
| | ETC) |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |