2004-12-02 00:00:00IN ELEC FOR REVIEW.
 ************** UNSAT ******************
  
 WAREHOUSE PROJECT:
 5405 N. HAVERHILL
 04110993
  
 REVIEWED FOR CODE COMPLIANCE UNDER 2002
 NEC.
  
 1)NOTE: PLEASE SEE UNIT #2, SHOWS TO BE
 FUTURE UNIT, YET MEZZ FLR AREA SHOWS
 LTS, BUT NOT TO ANY CIRCUITS?
 PLEASE CLARIFY.
  
 2)NOTE: PLEASE SEE UNITS #'S 13,26
 INDICATE SHOW ROOMS. PLEASE SEE 210.62
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED DIRECTLY ABOVE A SHOW WINDOW
 FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA
 MEASURED HORIZONTALLY AT ITS MAXIMUM
 WIDTH.
 SHOW WINDOWS USUALLY EXTEND FROM FLOOR
 TO CEILING FOR MAXIMUM DISPLAY. TO
 DISCOURAGE FLOOR RECEPTACLES AND
 UNSIGHTLY EXTENSION CORDS LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE A SHOW
 WINDOW, AND ONE RECEPTACLE IS REQUIRED
 FOR EVERY 12 LINEAR FT OR ?MAJOR
 FRACTION THEREOF? (6 FT OR MORE). SEE
 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS
 FOR SHOW WINDOWS.
 IT IS NOTEDON ONE OF THE PANEL
 SCHEDULES FOR L-26 "SHOWROOM RECEPTS,
 HOWEVER THESE APPEAR TO BE CLOSE TO FLR
 LEVEL?
  
 3)NOTE: PLEASE INDICATE CIRCUITING FOR
 ALL A/C EQUIPMENT. PLEASE SEE THERE ARE
 SOME A/C COND UNITS SHOWN ON ROOF, YET
 THESE DO NOT SHOW ANY HOOK-UPS, CIRCUITS
 ETC.?
 PLEASE SEE 440.11 WHICH REQUIRES
 DISCONNECTING MEANS CAPABLE OF
 DISCONNECTING AIR-CONDITIONING AND
 REFRIGERATING EQUIPMENT, INCLUDING
 MOTOR-COMPRESSORS AND CONTROLLERS FROM
 THE CIRCUIT CONDUCTORS.
  
 4)NOTE: PLEASE SEE ALL OPTS AS SHOWN ON
 E-1.08. IF ANY OF THESE OPTIONS ARE
 TAKENAND DIFFER FROM PLANS SHOWN, THEN
 PLANS WILL BE REQUIRED TO BE REVISED
 BEFORE ROUGH FOR WHICH OPTION IS TAKEN
 FOR WHICH UNIT. THIS IS ONLY A NOTE
 GIVEN AT THIS TIME.
  
 5)NOTE: PLEASE SEE 250.50 FOR REQUIRED
 POINTS OF ATTACHMENT FOR GROUNDING
 ELECTRODE SYSTEM.
 IF AVAILABLE ON THE PREMISES AT EACH
 BUILDING OR STRUCTURE SERVED, EACH ITEM
 IN 250.52(A)(1) THROUGH (A)(6) SHALL BE
 BONDED TOGETHER TO FORM THE GROUNDING
 ELECTRODE SYSTEM. CONCRETE-ENCASED
 ELECTRODE,METAL UNDERGROUND WATER PIPE,
 ETC.
  
 6)NOTE: PLEASE SEE THERE IS AN EQUIPMENT
 GROUNDING CONDUCTOR SHOWN FROM FPL
 TRANSFORMER TO MAIN # 2.
 PLEASE SEE 250.6,250.24
 OBJECTIONABLE CURRENT OVER GROUNDING
 CONDUCTORS.
 A PREMISES WIRING SYSTEM SUPPLIED BY A
 GROUNDED AC SERVICE SHALL HAVE A
 GROUNDING ELECTRODE CONDUCTOR CONNECTED
 TO THE GROUNDED SERVICE CONDUCTOR, AT
 EACH SERVICE, IN ACCORDANCE WITH
 250.24(A)(1) THROUGH (A)(5).
 THE CONNECTION SHALL BE MADE AT ANY
 ACCESSIBLE POINT FROM THE LOAD END OF
 THE SERVICE DROP OR SERVICE LATERAL TO
 AND INCLUDING THE TERMINAL OR BUS TO
 WHICH THE GROUNDED SERVICE CONDUCTOR IS
 CONNECTED AT THE SERVICE DISCONNECTING
 MEANS.
  
 7)NOTE: PLEASE SEE NOTE #9 FOR RISER
 DIAGRAM ON E 1.10.
 PLEASE SEE 250.122 FOR SIZING OF THE
 EQUIPMENT GROUNDING CONDUCTOR.
 COPPER, ALUMINUM, OR COPPER-CLAD
 ALUMINUM EQUIPMENT GROUNDING CONDUCTORS
 OF THE WIRE TYPE SHALL NOT BE SMALLER
 THAN SHOWN IN TABLE 250.122 BUT SHALL
 NOT BE REQUIRED TO BE LARGER THAN THE
 CIRCUIT CONDUCTORS SUPPLYING THE
 EQUIPMENT.
 SOME SHOWN AS #10 ON 100A OCP ETC.
 PLEASE SEE NOTE #17.
  
 8)NOTE: PLEASE CORRELATE RISER DIAGRAM
 EQUIPMENT SIZES.
 RISER SHOWS SOME 100A FEEDS TO 60A
 DISCONNECTING MEANS. PLEASE SEE
 EQUIPMENT MUST BE RATED FOR FEED.
 PLEASE SEE 1-6,14-19= 100A FEEDS TO 60A
 DISC'S. #20&21 150A FEEDS TO 100A
 DISC'S.????
  
 9)NOTE: PLEASE VERIFY SERVICE LOCATION
 ON PLANS. THIS COULD NOT BE LOCATED.
 PLEASE SEE 230.72 FOR GROUPING OF
 MAINS.
 PLEASE ALSO SEE 230.70 THE SERVICE
 DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION EITHER
 OUTSIDE OF A BUILDING OR STRUCTURE OR
 INSIDE NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS.
 THE TWO TO SIX DISCONNECTS AS PERMITTED
 IN 230.71 SHALL BE GROUPED. EACH
 DISCONNECT SHALL BE MARKED TO INDICATE
 THE LOAD SERVED.
  
 10)NOTE: PLEASE SHOW LOCATION OF
 DISCONNECTS, TRANSFORMERS IN UNITS.
 THESE COULD NOT BE LOCATED ON PLANS.
 215.5
  
 11)NOTE: PLEASE SEE 250.30 FOR GROUNDING
 OF TRANSFOMERS.
 GROUNDING SEPARATELY DERIVED
 ALTERNATING-CURRENT SYSTEMS.
 A SEPARATELY DERIVED AC SYSTEM THAT IS
 GROUNDED SHALL COMPLY WITH 250.30(A)(1)
 THROUGH (6). PLEASE SHOW THE ATTACHMENT
 ON RISER.
  
 12)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%.FEEDERS SHALL BE PROTECTED
 AGAINST OVERCURRENT IN ACCORDANCE WITH
 THE PROVISIONS OF PART I OF ARTICLE 240.
 WHERE A FEEDER SUPPLIES CONTINUOUS LOADS
 OR ANY COMBINATION OF CONTINUOUS AND
 NONCONTINUOUS LOADS, THE RATING OF THE
 OVERCURRENT DEVICE SHALL NOT BE LESS
 THAN THE NONCONTINUOUS LOAD PLUS 125
 PERCENT OF THE CONTINUOUS LOAD.
 THE AMPACITY OF THE SERVICE-ENTRANCE
 CONDUCTORS BEFORE THE APPLICATION OF ANY
 ADJUSTMENT OR CORRECTION FACTORS SHALL
 NOT BE LESS THAN EITHER (1) OR (2).
 LOADS SHALL BE DETERMINED IN ACCORDANCE
 WITH ARTICLE 220. AMPACITY SHALL BE
 DETERMINED FROM 310.15. THE MAXIMUM
 ALLOWABLE CURRENT OF BUSWAYS SHALL BE
 THAT VALUE FOR WHICH THE BUSWAY HAS BEEN
 LISTED OR LABELED.
 (1) THE SUM OF THE NONCONTINUOUS LOADS
 PLUS 125 PERCENT OF CONTINUOUS LOADS
 (2) THE SUM OF THE NONCONTINUOUS LOAD
 PLUS THE CONTINUOUS LOAD IF THE
 SERVICE-ENTRANCE CONDUCTORS TERMINATE IN
 AN OVERCURRENT DEVICE WHERE BOTH THE
 OVERCURRENT DEVICE AND ITS ASSEMBLY ARE
 LISTED FOR OPERATION AT 100 PERCENT OF
 THEIR RATING.
 THIS WILL BE FOR INDIVIUAL UNITS AND
 HOUSE PANELS.
  
 13)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER EACH MAIN.
 PLEASE SHOW LOAD CALCULATIONS, PLEASE
 SHOW PER 220.3,220.10,220.11,220.13
 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
 PLEASE ALSO INDICATE LOAD FOR EACH
 PANEL, ON THAT PARTICULAR PANEL
 SCHEDULE.
 PLEASE SEE THERE IS A PANEL "X" WHICH IS
 NOTED FOR SOME TYPICAL UNITS, HOWEVER
 THERE ARE CIRCUITS AND LOADS INDICATED
 ON SOME OF THESE UNITS WHICH ARE NOT
 SHOWN ON THIS "TYPICAL" PANEL
 SCHEDULE.?
 PLEASE CORRELATE. ONE UNIT NOTED,#13
  
 14)NOTE: PLANS CONTAIN NOTES IN MANY
 LOCATION WITH REFERENCE TO EXISTING
 SERVICE AND EXISTING PHASE 1, YET THE
 TITLE BLOCK AND PLANS REFERENCE THIS AS
 BEING PHASE -1. ??
 PLEASE SEE LOAD CALCS INDICATE
 "EXISTING" BUILDING CAPACITY???
 PLEASE SEE E1.10,1.09
  
 15)NOTE: PLEASE SEE SPRINKLER MONITOR
 PANEL DETAIL. PLEASE SEE MISSING
 EQUIPMENT GROUNDING PER 250.110
 EXPOSED NON?CURRENT-CARRYING METAL PARTS
 OF FIXED EQUIPMENT LIKELY TO BECOME
 ENERGIZED SHALL BE GROUNDED.
  
 16)NOTE: PLEASE CLARIFY IF FIRE
 SPRINKLER PIPING IS METAL? PLEASE SEE
 250.104 .THE METAL WATER PIPING SYSTEM
 SHALL BE BONDED AS REQUIRED IN (1), (2),
 (3), OR (4) OF THIS SECTION. THE BONDING
 JUMPER(S) SHALL BE INSTALLED IN
 ACCORDANCE WITH 250.64(A), (B), AND (E).
 THE POINTS OF ATTACHMENT OF THE BONDING
 JUMPER(S) SHALL BE ACCESSIBLE.
  
 17)NOTE: PLEASE SEE 408.16.EACH LIGHTING
 AND APPLIANCE BRANCH-CIRCUIT PANELBOARD
 SHALL BE INDIVIDUALLY PROTECTED ON THE
 SUPPLY SIDE BY NOT MORE THAN TWO MAIN
 CIRCUIT BREAKERS OR TWO SETS OF FUSES
 HAVING A COMBINED RATING NOT GREATER
 THAN THAT OF THE PANELBOARD.
 PLEASE SEE MOST PANELS ARE SHOWN AS
 MLO.
 PLEASE ALSO SEE 240.21
  
 18)NOTE: PLEASE SEE MOST OF THE WATER
 HEATERS SHOWN INDICATE 40A OCP FOR 6KW
 UNITS WHICH IS FINE, YET THERE ARE A
 COUPLE WITH 50A OCP. PLEASE SEE MAX OCP
 FOR WATER HEATER IS 150%. PLEASE ADJUST
 OCP.A BRANCH CIRCUIT SUPPLYING A FIXED
 STORAGE-TYPE WATER HEATER THAT HAS A
 CAPACITY OF 450 L (120 GAL) OR LESS
 SHALL HAVE A RATING NOT LESS THAN 125
 PERCENT OF THE NAMEPLATE RATING OF THE
 WATER HEATER.
 IF THE BRANCH CIRCUIT SUPPLIES A SINGLE
 NON?MOTOR-OPERATED APPLIANCE, THE RATING
 OF OVERCURRENT PROTECTION SHALL BE 150%
 MAX . 422.11
  
 19)NOTE: PLEASE SEE HOUSE PANEL "HP-1"
 DOES NOT INDICATE FEED FOR TRANSFORMER
 TO SPRINKLER MONT PANEL?
 PLEASE SHOW. 215.5
  
 20)NOTE: PLEASE SEE ALL LOADS FOR ALL
 AHU'S ON PANEL SCHEDULES. SOME SHOW
 ACTUAL LOADS, SOMEDO NOT INDICATE FULL
 KW LOAD FOR A/C UNITS??
 PLEASE CORRELATE ALL.
 215.5
  
 21)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS, DISCONNECTS. ETC.
 PLEASE SEE UNIT #1 ON RISER INDICATES A
 400A DISC , YET UNIT #1IS 100A'S??
 SHOWS UNIT #2 AS 100A AND PLANS INDICATE
 #2 AS 400A.
  
 22)NOTE: PLEASE SEE A/C LOAD/DISC ON
 PLANS, SHOWN FOR 50A LOAD?
  
 23)NOTE: PLEASE SEE WIND LOADING FOR
 POLES ARE LISTED AS 120MPH. PLEASE SEE
 WE ARE UNDER THE FBC 140 MPH RATING.
 PLEASE SUBMIT WIND LOADS AND SPECS FOR
 SITE LIGHTING POLES FOR BLDG REVIEW.
 THIS IS REQUIRED AT THIS TIME. PLEASE
 ALSO ADJUST ELECTRICAL PLANS FOR 140
 MPH.
 LIGHT POLES ARE ALSO NOTED AS MENTIONING
 TO MATCH "EXISTING" PHASE-1 ??
  
 24)NOTE: PLEASE SEE "L-26" ON E1.12 DOES
 NOT INDICATE BUS-RATING.?
 215.5
  
 25)NOTE: PLEASE ALSO SEE CIRCUITING OF
 EM/EXT LTS.
 PLEASE SEE 700.12E FOR CIRCUITING
 REQUIREMENTS.
 INDIVIDUAL UNIT EQUIPMENT FOR EMERGENCY
 ILLUMINATION SHALL CONSIST THE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
  
 26)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SEE BLDG REVIEW NOTES FOR
 REQUIREMENTS OF POSSIBLE "SPEACIAL
 INSPECTOR" AND NEEDING THREE (3) SETS OF
 PLANS.
  
 27)NOTE: PLEASE SEE POSSIBLE NOTES FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.(FIRE,BLDG
 ETC)
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717